2002-11-25 00:00:00 | MECH REVISION PERMIT 02040200 | | REVISED PLANS SUBMITTED ARE "REVERSE" | | OF APPROVED SET.PLAN INDICATES A 4 TON | | UNIT WHILE ENERGY & MANUCAL J CALCS | | REFLECT A 5 TON. PLEASE SUBMIT REVISED | | CALCS TO COINCIDE WITH PLANS. |
|