Plan Review Notes For Permit 02040189 |
Permit Number |
02040189 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-25 00:00:00 | ****************** UNSAT ************ | | | | 1)NOTE: PLEASE NOTE THAT THE PLANS ARE | | SHOWING THE 96 NEC CODE ARTS. PLEASE | | CORRELATE WITH THE 99 NEC. | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- | | ING AIC RATING AT 22.00? MISPRINT? | | SHOULD SHOW 22,000 | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | 4 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS. PER 210-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|