2002-04-25 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT THE PLANS ARE
 SHOWING THE 96 NEC CODE ARTS. PLEASE
 CORRELATE WITH THE 99 NEC.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE SHOW-
 ING AIC RATING AT 22.00? MISPRINT?
 SHOULD SHOW 22,000
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS. PER 210-12
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  