Plan Review Notes
Plan Review Notes For Permit 02040187
Permit Number 02040187
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-25 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE ARTS REF.
 IN NOTES ARE FROM THE 96 NEC. PLEASE
 CORRELATE WITH THE 99 NEC.
  
 2)NOTE: PLEASE NOTE THAT THE AIC RATING
 IS SHOWN AS 22.00, MISPRINT? SHOULD BE
 22,000 AIC .
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS PER 210-12
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372