Plan Review Notes
Plan Review Notes For Permit 02040184
Permit Number 02040184
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-26 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NEC ARTS REF.
 ARE FORM THE 96 NEC, PLEASE CORRELATE
 TO THE 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING SHOWN AS 22.00, SHOULD BE 22,000?
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372