Plan Review Notes
Plan Review Notes For Permit 02040130
Permit Number 02040130
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 SEC 424.2 PRIVATE
 POOLS
  
 1) PLEASE ADJUST NOTES AND DETAILS FOR
 POOL PLANS FOR REVIEW.
 A)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 B)
 FBC-2001 SEC 424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 C)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 2) PLEASE SUBMIT AN ISOMETRIC FOR THE
 POOL EQUIPMENT AND PIPING. INDICATE PIPE
 SIZES, VALVES, VENTS, BYPASSES AND RE-
 LATED PUMPS, FILTERS, HEATER EXT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377