Plan Review Notes For Permit 02040130 |
Permit Number |
02040130 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 SEC 424.2 PRIVATE | | POOLS | | | | 1) PLEASE ADJUST NOTES AND DETAILS FOR | | POOL PLANS FOR REVIEW. | | A) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | B) | | FBC-2001 SEC 424.2.7.1 POOL CIRCULATING | | PUMPS SHALL BE EQUIPPED ON THE INLET | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | STRAINER WHEN USED WITH A PRESSURE FIL- | | TER. (DETAIL) | | C) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 2) PLEASE SUBMIT AN ISOMETRIC FOR THE | | POOL EQUIPMENT AND PIPING. INDICATE PIPE | | SIZES, VALVES, VENTS, BYPASSES AND RE- | | LATED PUMPS, FILTERS, HEATER EXT. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|