Plan Review Notes For Permit 02040098 |
Permit Number |
02040098 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-10 00:00:00 | ******************UNSAT!**************** | | | | 1} PLEASE NOTE MISSING OUTLET FOR | | A/C EQUIPMENT. PER 210-63 AND/OR SECTION | | 306 OF THE MECHANICAL CODE. | | | | | | 2} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 3} PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | 4} NOTE AIC RATING @ 22.00 ? | | | | 5} THE CODE ARTICLES NOTED IN THE | | ELECTRICAL NOTES ARE INCORRECT. | | | | PLEASE ADDRESS THESE ISSUES AND RESUBMIT | | FOR REVIEW. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|