Plan Review Notes
Plan Review Notes For Permit 02040098
Permit Number 02040098
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-10 00:00:00******************UNSAT!****************
  
 1} PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 3} PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4} NOTE AIC RATING @ 22.00 ?
  
 5} THE CODE ARTICLES NOTED IN THE
 ELECTRICAL NOTES ARE INCORRECT.
  
 PLEASE ADDRESS THESE ISSUES AND RESUBMIT
 FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392