2002-04-25 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE WRONG CODES
 ARE REFERENCED. 96 NEC SHOWN AND WE ARE
 UNDER THE 99 NEC. PLEASE CORRECT.
  
 2)NOTE: PLEASE THAT THE AIC RATING IS
 SHOWN AS 22.00 INSTEAD OF 22,000 AIC.
 A MISPRINT.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS.
 SCHEDULE. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW