2002-04-25 00:00:00BUILDING DENIED
  
 FL BLD CODE 104.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1) PROVIDE FLOOR PLANS INDICATING THE
 EXISTING 1ST AND 2ND FLOORS.
  
 2) INDICATE THE INTERIOR BEARING WALLS.
  
 3) PROVIDE A WALL SECTION AT THE LOAD
 BEARING COLUMN,INDICATING THE FOUNDATION
 BENEATH, UPLIFT CONNECTORS FOR CONTINOUS
 LOAD PATH, ATTACHMENT AT TOP AND BOTTOM,
 ETC.
  
 4) PROVIDE DETAILS INDICATING THE
 CONSTRUCTION OF THE 12"X 12" COLUMNS.
 (MATERIALS, FASTENERS, FASTENER SPACING,
 ETC.)
  
 5) INDICATE THE FASTENER SPACING FOR THE
 CONSTRUCTION OF THE TRIPLE 2X10 BEAM.
  
 6) INDICATE WHETHER WATER HEATER IS GAS
 OR ELECTRIC. NOTE: GAS WATER HEATER IS
 NOT ALLOWED IN SLEEPING ROOM. 01 FPC
 SECT.502.4.
  