2002-04-18 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT A LOCK OUT
 DEVICE SHOWN FOR WATER HEATERS IS NOT
 CONSIDERED PERMANENT.PLEASE NOTE THAT
 ANY WATER HEATER THAT IS NOT WITHIN
 SIGHT REQ`S A DISCONNECT.
  
 2)NOTE: PLEASE NOTE MISSING SD`S INSIDE
 BEDROOMS. NFPA-72 2-2..1.1.1
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 4)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
  
 PLEASE SUBMTI THE ABOVE INFORMATION FOR]
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  