Plan Review Notes For Permit 02031652 |
Permit Number |
02031652 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-20 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SHT P-1 WATER HEATER DETAIL, 1" PAN | | DRAIN REQUIRED. | | 2) SHT P-2 DRAIN PAN DETAIL, 1" PAN | | DRAIN REQUIRED. | | 3) SHT P-3 WATER RISER DIAGRAM, AIR | | CHAMBERS ARE A QUICK FIX AND DO NOT WORK | | BUT IF USED THEY SHALL BE ACCESSIBLE AND | | RECHARGEABLE PER SEC 607.8.3. (SEE ATT- | | ACHED SHEETS FOR APPROVED AIR CHAMBER) | | APPROVED WATER HAMMER ARRESTORS DO NOT | | REQUIRE ACCESS AND DO NOT REQUIRE SERV- | | ICE AND IF USED THEY SHALL BE LOCATED IN | | AN "EFFECTIVE RANGE" CLOSE TO FIXTURE | | NOT AT TOP OF DROP. THIS IS TYPICAL ON | | SHTS P-4, P-5, & P-6 ALSO. | | 4) SHT P-4 SANITARY RISER DIAGRAM, 3RD | | FLOOR BATHROOM SHALL BE TAKEN OFF STACK | | BELOW KITCHEN SINK. THIS IS TYPICAL ON | | SHT P-5, SHT P-6 AND P-7 AT WASH MACHINE | | 5) SHT P-4 SANITARY RISER DIAGRAM, | | PIPING BELOW 2ND FLOOR CONFUSING. SEEMS | | THE 3" RUNS INTO A TEE WITH FLOW COMMING | | FROM TWO DIRECTIONS. THEN WHEN IT SHOULD | | TURN TO THE WASH MACHINE IT TEES AGAIN. | | WHERE DOES THE PIPE TO THE RIGHT OF THE | | TEE GO?? | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|