Plan Review Notes For Permit 02031652
Permit Number 02031652
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-02 00:00:001) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATIONS. PLEASE INDICATE FIRE
 HYDRANT LOCATIONS ON SITE PLAN. WET
 FIRE HYDRANTS ARE REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
 2) BUILDING ADDRESSES REQUIRED ON THE
 TOWNHOUSES. NUMBERS ARE TO BE AT LEAST
 3" HIGH.
 3) ELECTRIC POWERED SMOKE DETECTORS
 SHALL BE INSTALLED OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS AND ALL LEVELS OF THE
 DWELLING.
 4) STORAGE UNDER STAIRS NOT ALLOWED. IF
 ALLOWED, STORAGE AREA TO BE AT LEAST
 ONE HOUR FIRE RATED.
 5) NFPA 1 DEFINES "THAT WHEREVER THERE
 ARE THREE OR MORE LIVING UNITS IN A
 BUILDING, THE BUILDING IS CONSIDERED AN
 APARTMENT BUILDING. THE FIRE SPRINKLER
 SYSTEMS IN THESE UNITS MUST BE 13R
 TYPES.
 6) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR THE BALCONY RAILINGS.
 7) NO FIRE DEPARTMENT CONNECTION COULD
 BE LOCATED FOR BUILDING 6.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEMS.
 9) PLEASE EXPLAIN VOID UNDER STAIRS.
 10) PLEASE EXPLAIN 10" TREADS. NEW
 STAIRS ARE TO HAVE 11" TREADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910