2002-05-02 00:00:00 | 1) SITE PLAN DOES NOT INDICATE FIRE |
| HYDRANT LOCATIONS. PLEASE INDICATE FIRE |
| HYDRANT LOCATIONS ON SITE PLAN. WET |
| FIRE HYDRANTS ARE REQUIRED PRIOR TO, |
| DURING AND AFTER CONSTRUCTION. |
| 2) BUILDING ADDRESSES REQUIRED ON THE |
| TOWNHOUSES. NUMBERS ARE TO BE AT LEAST |
| 3" HIGH. |
| 3) ELECTRIC POWERED SMOKE DETECTORS |
| SHALL BE INSTALLED OUTSIDE EVERY |
| SLEEPING AREA IN THE IMMEDIATE VICINITY |
| OF THE BEDROOMS AND ALL LEVELS OF THE |
| DWELLING. |
| 4) STORAGE UNDER STAIRS NOT ALLOWED. IF |
| ALLOWED, STORAGE AREA TO BE AT LEAST |
| ONE HOUR FIRE RATED. |
| 5) NFPA 1 DEFINES "THAT WHEREVER THERE |
| ARE THREE OR MORE LIVING UNITS IN A |
| BUILDING, THE BUILDING IS CONSIDERED AN |
| APARTMENT BUILDING. THE FIRE SPRINKLER |
| SYSTEMS IN THESE UNITS MUST BE 13R |
| TYPES. |
| 6) PLEASE PROVIDE PRESCRIPTIVE CODE |
| REQUIREMENTS FOR THE BALCONY RAILINGS. |
| 7) NO FIRE DEPARTMENT CONNECTION COULD |
| BE LOCATED FOR BUILDING 6. |
| 8) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE SPRINKLER SYSTEMS. |
| 9) PLEASE EXPLAIN VOID UNDER STAIRS. |
| 10) PLEASE EXPLAIN 10" TREADS. NEW |
| STAIRS ARE TO HAVE 11" TREADS. |
| |