2002-04-26 00:00:00 | THE GENERAL NOTES ON SHEET A1 OF THE |
| PLANS DECLARE TYPE V UNPROTECTED |
| CONSTRUCTION AND A NFPA 13D FIRE |
| SPRINKLER SYSTEM.FOOTNOTE (D) TO |
| TABLE500 PROHIBITS A 13D OR 13R SYSTEM |
| FOR HEIGHT MODIFICATIONS. |
| |
| THE BUILDINGS MUST BE EITHER 1 HOUR |
| PROTECTED WITH A 13D SYSTEM OR A FULL |
| 13 SYSTEM TO BE THREE STORIES.PLEASE |
| REVISE AS NECESSARY. |
| |
| SECTIONS ON SHEET A6 SHOW AN EXISTING |
| RETAINING WALL.THE PROPOSED PROBERTY |
| LINES SHOW THE RETAINING WALL FOOTING |
| TO BE ENCROACHING ON THE NEIGHBORING |
| PROPERTY.PROVIDE A METHOD TO RESOLVE |
| OWNERHIP AND RESPONSIBILITY. |
| |
| SAME.PROVIDE AN ENGINEERING ANALYSIS |
| OF THE SUITABILITY OF THE EXISTING |
| WALL TO ASSUME THE ADDED FOUNDATION |
| LOADS OF THE BUILDINGS.INCLUDE THE |
| WATER PROOFING AND/OR DAMP PROOFING |
| REQUIRED BY SBC 1814.1 |
| |
| BUILDINGS NUMBERED 1,4,6, AND 7 HAVE |
| EXTERIOR WALL OPENINGS EXCEEDING THE |
| 40% ALLOWED BY SBC TABLE 600 ON UNITS |
| LABELED "E".PLEASE REVISE AS |
| NECESSARY. |
| |
| WITH AN ASSUMED PROPERTY, THERE IS NONE |
| INDICATED ON THE PLANS, BETWEEN |
| BUILDINGS PAIRED, 1&2 2&3 3&4 ETC. THE |
| ALLOWABLE EXTERIOR WALL OPENINGS FOR |
| TABLE 600 ARE EXCEEDED.PLEASE REVISE |
| AS NECESSARY. |
| |
| PLEASE PROVIDE THE SOIL REPORTS FOR |
| THESE BUILDINGS.SEE SBC 104.2. |
| |
| PROVIDE THE NOTICE OF ACCEPTANCE AND |
| TEST REPORTS FOR THE WINDOWS, DOORS AND |
| ROOF COVERING. |
| |
| SHOW THE SOIL TERMITE TREATMENT IN |
| ACCORDANCE WITH SBC 2304 AS AMENDED BY |
| THE CITY. |
| |
| SHEET S2 CITES ASCE 7-98, THE 1997 SBC |
| INVOKES ASCE 7-95.PLEASE REVISE |
| ACCORDINGLY AND DEMONSTRATE COMPLIANCE |
| WITH 7-95.ALTERNATIVELY, REVISE THE |
| BUILSDINGS TO COMPLY WITH THE 2001 FBC. |
| |
| THE EMERGENCY EGRESS FOR BUILDINGS 8 |
| AND12 INTO THE ENCLOSED COURTYARD DOES |
| NOT MEET THE RESCUE REQUIREMENTS OF SBC |
| 1005.4.PLEASE REVISE AS NECESSARY. |
| |
| SEPARATE SURVEYS ARE REQUIRED FOR EACH |
| TOWNHOUSE UNIT. |
| |
| GIVEN THE SIZE AND SCOPE OF THIS PROJECT |
| A RESIDENT INSPECTOR WILL BE REQUIRED. |
| CONTACT DON NEELY AT 561-659-8096 EXT |
| 8333 FOR MORE INFORMATION. |
| |