Plan Review Notes
Plan Review Notes For Permit 02031652
Permit Number 02031652
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-26 00:00:00THE GENERAL NOTES ON SHEET A1 OF THE
 PLANS DECLARE TYPE V UNPROTECTED
 CONSTRUCTION AND A NFPA 13D FIRE
 SPRINKLER SYSTEM.FOOTNOTE (D) TO
 TABLE500 PROHIBITS A 13D OR 13R SYSTEM
 FOR HEIGHT MODIFICATIONS.
  
 THE BUILDINGS MUST BE EITHER 1 HOUR
 PROTECTED WITH A 13D SYSTEM OR A FULL
 13 SYSTEM TO BE THREE STORIES.PLEASE
 REVISE AS NECESSARY.
  
 SECTIONS ON SHEET A6 SHOW AN EXISTING
 RETAINING WALL.THE PROPOSED PROBERTY
 LINES SHOW THE RETAINING WALL FOOTING
 TO BE ENCROACHING ON THE NEIGHBORING
 PROPERTY.PROVIDE A METHOD TO RESOLVE
 OWNERHIP AND RESPONSIBILITY.
  
 SAME.PROVIDE AN ENGINEERING ANALYSIS
 OF THE SUITABILITY OF THE EXISTING
 WALL TO ASSUME THE ADDED FOUNDATION
 LOADS OF THE BUILDINGS.INCLUDE THE
 WATER PROOFING AND/OR DAMP PROOFING
 REQUIRED BY SBC 1814.1
  
 BUILDINGS NUMBERED 1,4,6, AND 7 HAVE
 EXTERIOR WALL OPENINGS EXCEEDING THE
 40% ALLOWED BY SBC TABLE 600 ON UNITS
 LABELED "E".PLEASE REVISE AS
 NECESSARY.
  
 WITH AN ASSUMED PROPERTY, THERE IS NONE
 INDICATED ON THE PLANS, BETWEEN
 BUILDINGS PAIRED, 1&2 2&3 3&4 ETC. THE
 ALLOWABLE EXTERIOR WALL OPENINGS FOR
 TABLE 600 ARE EXCEEDED.PLEASE REVISE
 AS NECESSARY.
  
 PLEASE PROVIDE THE SOIL REPORTS FOR
 THESE BUILDINGS.SEE SBC 104.2.
  
 PROVIDE THE NOTICE OF ACCEPTANCE AND
 TEST REPORTS FOR THE WINDOWS, DOORS AND
 ROOF COVERING.
  
 SHOW THE SOIL TERMITE TREATMENT IN
 ACCORDANCE WITH SBC 2304 AS AMENDED BY
 THE CITY.
  
 SHEET S2 CITES ASCE 7-98, THE 1997 SBC
 INVOKES ASCE 7-95.PLEASE REVISE
 ACCORDINGLY AND DEMONSTRATE COMPLIANCE
 WITH 7-95.ALTERNATIVELY, REVISE THE
 BUILSDINGS TO COMPLY WITH THE 2001 FBC.
  
 THE EMERGENCY EGRESS FOR BUILDINGS 8
 AND12 INTO THE ENCLOSED COURTYARD DOES
 NOT MEET THE RESCUE REQUIREMENTS OF SBC
 1005.4.PLEASE REVISE AS NECESSARY.
  
 SEPARATE SURVEYS ARE REQUIRED FOR EACH
 TOWNHOUSE UNIT.
  
 GIVEN THE SIZE AND SCOPE OF THIS PROJECT
 A RESIDENT INSPECTOR WILL BE REQUIRED.
 CONTACT DON NEELY AT 561-659-8096 EXT
 8333 FOR MORE INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPEDBY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.