2002-03-26 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} AMPERAGE RATING ON THE "METER/MAIN"
  
 3} GROUNDING METHOD USED FOR NEW AND
 EXISTING SERVICES.MUST COMPLY WITH
 250-30.
  
 4} WHAT IS THE OCP ON THE CONDUCTORS
 REFEEDING THE HOUSE PANEL?
  
 5} INDICATE WHERE THE POOL EQUIPMENT IS
 FED FROM,SHOW WIRE SIZE,CONDUIT TYPE AND
 SIZE AND OCP.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW