2002-04-08 00:00:00**************DENIED********************
  
 ADDITIONAL INFORMATION REQUIRED
 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO
 DETERMINE COMPLIANCE PER 2001 FBC(M)
 504.5
 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
 3. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
  
 NOTE: DRYER AND BATH EXHAUST DUCTS SHALL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF