2002-03-27 00:00:002001 FBC, MECHANICAL & NFPA 96
  
 PROVIDE MANUFACTURER SUMITTAL DATA AND
 INSTALLATION INSTRUCTIONS FOR THE 3M
 FASTWRAP.INDICATE 1 OR 2 HR RATING.
  
 INDICATE LOCATION OF CLEANOUTS ON PLAN.
  
 PLEASE NOTE, EXHAUST OUTLETS SHALL BE
 LOCATED NOT LESS THAN 10 FT
 HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, PROPERTY LINES
 AND AIR INTAKE OPENINGS.
  