Plan Review Notes
Plan Review Notes For Permit 02031231
Permit Number 02031231
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-03-19 00:00:00A) IT WAS NOTED FROM THE PLANS THAT
 NO SMOKE DETECTORS EITHER ONES
 CONNECTED TO THE FIRE ALARM SYSTEM OR
 SINGLE STATION ONES WERE PRESENT IN THE
 UPSTAIR ROOMS. IT IS BELIEVED THAT
 SOME OF THE ROOMS MAY BE USED FOR
 SLEEPING PURPOSES. PLEASE BE ADVISED
 THAT NFPA 101, THE LIFE SAFETY CODE,
 2000 EDITION, SECTION 29.3.4.5,
 EXISTING DORMITORIES AND HOTELS,
 INDICATES " AN APPROVED SINGLE-STATION
 SMOKE ALARM SHALL BE INSTALLED IN
 EVERY GUEST ROOM AND EVERY LIVING AREA
 AND SLEEPING ROOM WITHIN A GUEST SUITE".
 " THESE ALARMS SHALL NOT BE REQUIRED
 TO BE INTERCONNECTED. SINGLE STATION
 SMOKE ALARMS WITHOUT A SECONDARY POWER
 SUPPLY POWER SOURCE SHALL BE PERMITTED".
 PLEASE ADVISE THIS OFFICE IN WRITING
 HOW COMPLIANCE WITH THIS CODE SECTION
 WILL BE ACCOMPLISHED.
  