1 |
|
Notes |
Date |
Text |
2002-03-20 00:00:00 | | | | | | | | | | | | | | | | | | | | | | | | | | | ****************UNSAT!****************** | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION AND RESUBMIT FOR REVIEW: | | | | 1} SIZE OF THE EXISTING SERVICE AND | | ADDITIONAL LOAD BEING ADDED TO THE | | SERVICE. | | | | 2} CIRCUIT NUMBERS AS THEY WILL APPEAR | | ON THE PANEL SCHEDULE. | | | | 3} CIRCUITING OF RECEPTACLES.COMPLY | | WITH210-52(B)(1),THROUGH 210-52(C)(5). | | | | 4} DRAWINGS TO COMPLY WITH 104.2 OF THE | | CITY AMMENDMENTS. THE CABINET DETAILS | | NEED TO BE DRAWN CLEARLY ENOUGH TO | | DETERMI | | NE CORRECT RECEPTACLE LOCATIONS. |
|