Plan Review Notes
Plan Review Notes For Permit 02031089
Permit Number 02031089
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT SH-1 GENERAL NOTES #6 TO READ
 FBC-2001 PLUMBING.
 2) SHT A3_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 3) SHT A3A_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER). SECTION 604.9
 4) SHT A3_MP-3 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL
 5) SHT A3_MP-3 WATER HEATER DETAIL. SEC
 504.7.1 THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR AIR GAP FITTING LO-
 CATED IN THE SAME ROOM AS THE HEATER.
 6) SHT A2_MP-1 SANITARY RISER DIAGRAM.
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 7) SHT A2_MP-1 WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES AR UTILI-
 ZED. (WASH MACHINES, DISHWASHERS, ICE
 MAKERS.) SECTION 604.9
 8) SHT A_MP-3 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 9) SHT A_MP-3 WATER HEATER DETAIL. THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE HEATER.
 10) SHT A1_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 11) SHT A1_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 12) SHT A1_MP-3 PLUMBING NOTES AND SPECS
 NOTE #1(B)TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 13) SHT A1_MP-3 WATER HEATER DETAIL. THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER. SECTION
 504.7.1 (RELIEF VALVES - P/T)
 14) SHT B_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 15) SHT B_MP-4 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 16) SHT B_MP-4 WATER HEATER DETAIL. RE-
 LIEF VENT - THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR A AIR GAP FITTING
 LOCATED IN THE SAME ROOM AS THE HEATER.
 SECTION 504.7.1.
  
 REVIEW BY KEN STEVENS