2002-04-19 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FHA AMEND-98 DESIGN MANUAL |
| |
| 1) SHT SH-1 GENERAL NOTES #6 TO READ |
| FBC-2001 PLUMBING. |
| 2) SHT A3_MP-1 SANITARY RISER DIAGRAM, |
| OPTIONAL LAUNDRY SINK TO RUN TO THE |
| RIGHT OF THE BLDG. DRAIN AWAY FROM WASH |
| MACHINE TO REFLECT FLOOR PLAN. |
| 3) SHT A3A_MP-1 WATER RISER DIAGRAM, |
| WATER HAMMER ARRESTORS SHALL BE INSTALL- |
| ED WHERE QUICK CLOSING VALVES ARE UTILI- |
| ZED. (WASH MACHINE, DISHWASHER, ICE |
| MAKER). SECTION 604.9 |
| 4) SHT A3_MP-3 PLUMBING NOTES AND SPECS. |
| NOTE #1(B) TO READ FBC-2001 PLUMBING, & |
| FHA AMEND-98 DESIGN MANUAL |
| 5) SHT A3_MP-3 WATER HEATER DETAIL. SEC |
| 504.7.1 THE DISCHARGE PIPE SHALL NOT |
| HAVE ANY TRAPPED SECTIONS AND SHALL HAVE |
| A VISIBLE AIR GAP OR AIR GAP FITTING LO- |
| CATED IN THE SAME ROOM AS THE HEATER. |
| 6) SHT A2_MP-1 SANITARY RISER DIAGRAM. |
| OPTIONAL LAUNDRY SINK TO RUN TO THE |
| RIGHT OF THE BLDG. DRAIN AWAY FROM WASH |
| MACHINE TO REFLECT FLOOR PLAN. |
| 7) SHT A2_MP-1 WATER RISER DIAGRAM. |
| WATER HAMMER ARRESTORS SHALL BE INSTALL- |
| ED WHERE QUICK CLOSING VALVES AR UTILI- |
| ZED. (WASH MACHINES, DISHWASHERS, ICE |
| MAKERS.) SECTION 604.9 |
| 8) SHT A_MP-3 PLUMBING NOTES AND SPECS. |
| NOTE #1(B) TO READ FBC-2001 PLUMBING, & |
| FHA AMEND-98 DESIGN MANUAL. |
| 9) SHT A_MP-3 WATER HEATER DETAIL. THE |
| DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP- |
| ED SECTIONS AND SHALL HAVE A VISIBLE AIR |
| GAP OR AIR GAP FITTING LOCATED IN THE |
| SAME ROOM AS THE HEATER. |
| 10) SHT A1_MP-1 SANITARY RISER DIAGRAM, |
| OPTIONAL LAUNDRY SINK TO RUN TO THE |
| RIGHT OF THE BLDG. DRAIN AWAY FROM WASH |
| MACHINE TO REFLECT FLOOR PLAN. |
| 11) SHT A1_MP-1 WATER RISER DIAGRAM, |
| WATER HAMMER ARRESTORS SHALL BE INSTALL- |
| ED WHERE QUICK CLOSING VALVES ARE UTILI- |
| ZED. (WASH MACHINE, DISHWASHER, ICE |
| MAKER) SECTION 604.9 |
| 12) SHT A1_MP-3 PLUMBING NOTES AND SPECS |
| NOTE #1(B)TO READ FBC-2001 PLUMBING, & |
| FHA AMEND-98 DESIGN MANUAL. |
| 13) SHT A1_MP-3 WATER HEATER DETAIL. THE |
| DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP- |
| ED SECTIONS AND SHALL HAVE A VISIBLE AIR |
| GAP OR AIR GAP FITTING LOCATED IN THE |
| SAME ROOM AS THE WATER HEATER. SECTION |
| 504.7.1 (RELIEF VALVES - P/T) |
| 14) SHT B_MP-1 WATER RISER DIAGRAM, |
| WATER HAMMER ARRESTORS SHALL BE INSTALL- |
| ED WHERE QUICK CLOSING VALVES ARE UTILI- |
| ZED. (WASH MACHINE, DISHWASHER, ICE |
| MAKER) SECTION 604.9 |
| 15) SHT B_MP-4 PLUMBING NOTES AND SPECS. |
| NOTE #1(B) TO READ FBC-2001 PLUMBING, & |
| FHA AMEND-98 DESIGN MANUAL. |
| 16) SHT B_MP-4 WATER HEATER DETAIL. RE- |
| LIEF VENT - THE DISCHARGE PIPE SHALL NOT |
| HAVE ANY TRAPPED SECTIONS AND SHALL HAVE |
| A VISIBLE AIR GAP OR A AIR GAP FITTING |
| LOCATED IN THE SAME ROOM AS THE HEATER. |
| SECTION 504.7.1. |
| |
| REVIEW BY KEN STEVENS |