2002-04-17 00:00:00 | CHECKLIST: |
| 1-DESIGN CRITERIA: |
| FBC 2001 SEC. 1606.2 SHALL NOT BE USED |
| TO DESIGN A "PARTIALLY ENCLOSED" BLDG. |
| SEE SEC. 1606.1.4.1 FBC 2001. |
| *THE ONLY DESIGN CRITERIA ACCEPTABLE |
| UNDER FBC 2001 IS ASCE 7-98 METHOD 2 - |
| ANALYTICAL PROCEDURE USING FIG. 6-3. |
| 2-TWO HR OVERHANG DETAIL FOR WD ASSEMBLY |
| USING CALCULATED RATINGS IS NOT |
| ACCEPTABLE. SEC. 709.6.1.2 FBC 2001. |
| 3-UPDATE ALL PLANS AND SPECIFICATIONS. |
| SEE COMMENTS ON PLANS. PLEASE, RETURN |
| REVIEWED SET TO EXPEDITE REVIEW. |
| 4-REVISE 2 HR FIRE RATED GLASS BLOCK |
| ASSEMBLY DETAIL FOR MODEL "C". SEE UL |
| LISTING FOR ASSEMBLY SPECIFICATIONS. |
| 5-REVISE STRUCTURAL BUCK DETAILS TO |
| SATISFY REQUIREMENTS OF SEC. 1707.4.4 |
| FBC 2001. |
| 6-PROVIDE COMPLETE SPECIFICATIONS FOR |
| CEILING INSTALLATION AT FRONT AND BACK |
| PORCHES. SEE ASTM C1063 FOR SPECIFIC |
| FASTENERS AND SPACING. |
| SEC. 2504.2 FBC 2001. |
| 7-CLARIFY GARAGE DOOR BUCK DETAIL. SEE |
| DET. 1/DS-1 AND DET. 4/S4. |
| 8-REVISE ENERGY CALCULATIONS: |
| A)UNDER ATTIC AREA. SEE SEC. 604.1.A.1 |
| OF CHAPTER 13 FBC 2001. |
| B)THIS IS MULTIFAMILY UNITS, NOT SINGLE |
| FAMILY. ALSO SPECIFY NUMBER OF UNITS. |
| 9-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. REPORT SUBMITTED WAS |
| DELETED FROM SBCCI LISTING. |
| B)HORIZONTAL ROLLING WINDOWS WHEN USED. |
| 10-LOTS 27, 26, 25, AND 24 DON'T COMPLY |
| WITH TABLE 600 FBC 2001 AT REAR ELEV. |
| 10'-0" DISTANCE FROM PROPERTY LINE |
| ALLOWS 20% OPENINGS ONLY. |
| 11-CONCRETE SLAB SPECIFICATIONS TO ADD |
| NOTE REQUIRING SUPPORTS AS REQUIRED ON |
| SECTION 1909.3 FBC 2001. |
| 12-UPDATE ALL CONNECTORS AS REQUIRED |
| WHEN SPECIFYING HUGHES OR SEMCO |
| CONNECTORS. THESE COMPANIES ARE OUT OF |
| BUSINESS. |
| |
| |
| |
| NOTES: |
| -DRAWINGS AND NOTES TO BE FILED UNDER |
| PERMIT #02031089. |
| -THESE COMMENTS APPLY TO PERMIT NUMBERS: |
| 02031089,02031088, 02031086, 02031084 |
| AND 02031083. |