2002-04-02 00:00:00***************DENIED*******************
 1. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
 2. PROVIDE CFM INFORMATION ON DRYER TO
 DETERMINE COMPLIANCE WITH 2001 FBC(M)
 504.5
 3. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
  
 NOTE: DRYER AND BATH EXHAUST DUCT SHAL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF