Plan Review Notes For Permit 02031086 |
Permit Number |
02031086 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-02 00:00:00 | *************DENIED******************* | | 1. SEER ON EQUIPMENT SCHEDULE DOES NOT | | MATCH SEER ON ENERGY CALCS | | 2. PROVIDE CFM INFORMATION ON DRYER TO | | DETERMINE COMPLIANCE WITH FBC(M) 504.5 | | 3. PROVIDE OUTSIDE AIR PER 2001 FBC(M) | | TABLE 403.3 | | | | NOTE: DRYER AND BATH EXHAUST DUCT SHALL | | NOT PENETRATE RATED PARTYWALL OR | | ADJACENT ROOF |
|