Plan Review Notes
Plan Review Notes For Permit 02031084
Permit Number 02031084
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-02 00:00:00**************DENIED*******************
 1. SEER ON EQUIPMENT DOES NOT MATCH SEER
 ON ENERGY CALCS
 2. PROVIDE CFM INFORMATION ON DRYER TO
 DETERMINE COMPLIANCE WITH 2001 FBC(M)
 504.5
 3. PROVIDE OUTSIDE AIR PER 2001 FBC(M)
 TABLE 403.3
  
 NOTE: DRYER AND BATH EXHAUST DUCT SHALL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF