Plan Review Notes
Plan Review Notes For Permit 02031083
Permit Number 02031083
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-02 00:00:00**************DENIED*******************
 1. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
 2. PROVIDE CFM INFORMATION ON DRYER TO
 SHOW COMPLIANCE WITH 2001 FBC(M) 504.5
 3. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
  
 NOTE: DRYER AND BATH EXHAUST DUCTS SHALL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF