Plan Review Notes
Plan Review Notes For Permit 02031080
Permit Number 02031080
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-02 00:00:00*************DENIED********************
  
 ADDITIONAL INFORMATION NEEDED
 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO
 DETERMINE COMPLIANCE REQUIREMENTS PER
 2001 FBC(M) 504.5
 2. PROVIDE OUTSIDE AIR PER SBC(M) TABLE
 403.3
 3. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
  
 NOTE: DRYER AND BATH EXHAUST DUCT SHALL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF