Plan Review Notes
Plan Review Notes For Permit 02031078
Permit Number 02031078
Review Stop M
Sequence Number 2
Notes
Date Text
2002-05-13 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02031106
  
 SEER ON ENERGY CALCS OKAY.
  
 OTHER COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW.
  
 1. O.A. CALCS. SHALL PROVIDE COMPLIANCE
 WITH 402.2 (4% OF THE FLOOR AREA BEING
 VENTILATED) OR TABLE 403.3 (MECHANICAL
 VENTILATION NOT INFILTRATION)
  
 2. DRYER CFM NOT PROVIDED.
  
 3. DRYER LENGTHS IN EXCESS OF CODE
 MINIMUM OF 25' PER 504.6. SUBMIT
 SPECIFIC MANUFACTURER SPECIFICATIONS OF
 ALLOWABLE LENGTH OF DUCT.
  
 4. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH PER
 307.2.4 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.