Plan Review Notes For Permit 02031076 |
Permit Number |
02031076 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-13 00:00:00 | MECHANICAL PERMIT 02031110 | | | | OTHER COMMENTS NOT ADDRESSED FROM | | PREVIOUS REVIEW. | | | | 1. SEER ON ENERGY CALCS STILL DO NOT | | MATCH SEER SHOWN ON EQUIPMENT SCHEDULE. | | | | 2. O.A. CALCS. SHALL PROVIDE COMPLIANCE | | WITH 402.2 (4% OF THE FLOOR AREA BEING | | VENTILATED) OR TABLE 403.3 (MECHANICAL | | VENTILATION NOT INFILTRATION) | | | | 3. DRYER CFM NOT PROVIDED. | | | | 4. DRYER LENGTHS IN EXCESS OF CODE | | MINIMUM OF 25' PER 504.6. SUBMIT | | SPECIFIC MANUFACTURER SPECIFICATIONS OF | | ALLOWABLE LENGTH OF DUCT. | | | | 5. SECONDARY DRAIN CONSPICUOUS POINT | | SHALL NOT BE BEHIND AHU CLOSET DOOR. IF | | NO SUITABLE CONSPICUOUS LOCATION IS | | AVAILABLE, A PAN WITH A FLOAT SWITCH PER | | 307.2.4 IS ACCEPTABLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|