2002-05-15 00:00:00 | APPROVED WITH PROVISO: |
| 1-TWO HOUR OVERHANG DETAIL FOR WOOD |
| ASSEMBLY USING CALCULATED RATINGS IS |
| NOT ALLOWED. SEE SECTION 709.6.1.2 |
| FBC 2001. REVISE AS REQUIRED. |
| 2-REVISE OR OMIT 2HR FIRE RATED GLASS |
| BLOCK DETAIL. SEE UL ASSEMBLY SPECS |
| FOR TWO HR FIRE RATED ASSEMBLY. |
| 3-REVISE BUCK DETAILS. SEE SECTION |
| 1704.4.2 FBC 2001 FOR SPECIFICATIONS |
| REGARDING THE EXTEND OF THE BUCK. |
| 4-PROVIDE COMPLETE SPECIFICATIONS FOR |
| INSTALLATION OF CEILINGS AT FRONT AND |
| REAR PORCHES. SEE ASTM C-1063 FOR |
| FASTENERS, TYPE, SIZE AND SPACING. |
| SECTION 2504.2 FBC 2001. |
| 5-CLARIFY GARAGE DOOR DETAIL. SEE DETAIL |
| 1/DS-1 AND DETAIL 4/S4. |
| 6-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE PRODUCT APPROVAL SUBMITTED |
| IS NOT GOOD. IT WAS DELETED FROM SBCCI |
| 7-UPDATE ALL CONNECTORS AS REQUIRED. |
| HUGHES OR SEMCO ARE OUT OF BUSINESS. |
| 8-APPLY FOR SEPARATE PERMITS FOR UNITS |
| TO HAVE SCREEN ENCLOSURES. |
| |
| NOTES: |
| *DRAWINGS AND COMMENTS TO BE FILED UNDER |
| PERMIT #02031076. |
| *THESE COMMENTS APPLY TO PERMIT #S: |
| 02031076, 02031077, 02031078 AND |
| 02031080. |