Date Text
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT BR_MP-1 SANITARY RISER DIAGRAM,
 MASTER BATH SHOWS 2 LAVS, ONLY 1 SHOWN
 ON FLOOR PLAN. (IF OPTIONAL, STATE ON
 PLAN)
 2) SHT BR_MP-1 WATER RISER DIAGRAM, RE-
 MOVE AIR CHAMBER AT WATER HEATER. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED
 WHERE QUICK CLOSING VALVES ARE UTILIZED.
 (WASH MACHINE, DISHWASHER, ICE MAKER)
 SECTION 604.9
 3) SHT B_MP-4 PLUMBING NOTES AND SPECS.,
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 4) SHT A_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 5) SHT A_MP-1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE INSTALLED
 WHERE QUICK CLOSING VALVES ARE UTILIZED.
 (WASH MACHINES, DISHWASHERS, ICE MAKERS)
 SECTION 604.9
 6) SHT A_MP-3 PLUMBING NOTES AND SPECS.,
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 7) SHT A1_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 8) SHT A1_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTIL-
 IZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER). SECTION 604.9
 9) SHT A1_MP-1 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 10) SHT B_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTIL-
 IZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 11) SHT B_MP-4 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 12) 504.7.1 THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR AIR GAP FITTING LO-
 CATED IN THE SAME ROOM AS THE WATER
 HEATER. SEE SHTS A_MP-3 & B_MP-4 WATER
 HEATER DETAILS.
  
 REVIEW BY KEN STEVENS