2002-04-06 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02031076 |
| LOTS: 75-78 |
| 8596 LINYARD CAY |
| |
| FL CODE= 2001 FLORIDA BUILDING CODE |
| FR HOUS= FAIR HOUSING ACT |
| |
| 1)- SOILS REPORT NOT SIGNED & SEALED, |
| 61G15-23.002 REQUIRES THE PROFESSIONAL |
| ENGINEER SHALL SIGN HIS NAME AND AFFIX |
| HIS SEAL TO ALL PLANS SPECIFICATIONS, |
| REPORTS OR DOCUMENTS PREPARED OR ISSUED |
| BY SAID REGISTRANT AND BEING FILED FOR |
| PUBLIC RECORD. |
| |
| 2)- STRUCTURAL CUT SECTIONS MISSING A |
| NEW CODE ELEMENT FL CODE 1909.3(2) |
| CONCRETE SLABS ON GROUND CONTAINING 6X6 |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3 OF THE SLAB, SHALL BE SUPPORT- |
| ED WITH AN APPROVED MATERIALS OR SUPPORT |
| AT SPACINGS TO NOT EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURES SPECIFICA- |
| TIONS. |
| 3)- STRUCURAL PLANS- HUGHES MANUFACTUR- |
| ING AS WELL AS SEMCO WERE BOUGHT OUT BY |
| USP CONNECTORS OVER A YEAR AGO. THERE |
| IS A NEW PRODUCT REFRENCE NUMBERS AND |
| NEW TESTING DATA. |
| 4)- SH-1 EGRESS TYPE WINDOW NOTES: INDIC |
| ATES A NOTE "DELTA 5" THAT ALL EXTERIOR |
| GLAZED OPENINGS SHALL COMPLY WITH THE |
| FBC 2001 ED CHAPTER 3? THREE IS TYPE |
| OF OCCUPANCIES? 1005.4 EMERGENCY ESCAPE |
| AND RESCUE OPENINGS. |
| 5)- SHEET SH-1WINDOW SCHEDULE INDICATE |
| A "I" 8" GLASS BLOCK TO BE A 2 HR RATING |
| SHEET DS-1 DETAILS GLASS BLOCK IN MODEL |
| "C". A 2 HR RATING? |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (5610659-8096X8412 |