Plan Review Notes For Permit 02030965 |
Permit Number |
02030965 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-15 00:00:00 | A) ENTIRE BUILDING IS REQUIRED TO BE | | FIRE SPRINKLER PROTECTED. | | B) THE FIRE DEPARTMENT CONNECTION IS TO | | NO MORE THAN 150 FEET FROM A FIRE | | HYDRANT. | | C) FIRE SPRINKLER PIPING THAT ENTERS | | THE STAIRWAY IS NOT TO INTERFERE WITH | | MINIMUM HEADROOM REQUIREMENTS. | | D) FIRE SPRINKLER HEADS IN GARAGE SHOULD | | BE WAX COATED. | | E) TWO SMALL BOXES ON THE SECOND AND | | THIRD FLOOR ARE TO BE FIRE SPRINKLER | | PROTECTED. THESE AREAS APPEAR TO BE | | LOCATED ABOVE THE FIRST FLOOR MECHANICAL | | ROOM. | | F) BACKFLOW DEVICE IS REQUIRED TO BE | | SUPERVISED WITH TAMPER SWITCHES AND | | A CHAIN AND LOCK. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|