Plan Review Notes
Plan Review Notes For Permit 02030965
Permit Number 02030965
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-03-15 00:00:00A) ENTIRE BUILDING IS REQUIRED TO BE
 FIRE SPRINKLER PROTECTED.
 B) THE FIRE DEPARTMENT CONNECTION IS TO
 NO MORE THAN 150 FEET FROM A FIRE
 HYDRANT.
 C) FIRE SPRINKLER PIPING THAT ENTERS
 THE STAIRWAY IS NOT TO INTERFERE WITH
 MINIMUM HEADROOM REQUIREMENTS.
 D) FIRE SPRINKLER HEADS IN GARAGE SHOULD
 BE WAX COATED.
 E) TWO SMALL BOXES ON THE SECOND AND
 THIRD FLOOR ARE TO BE FIRE SPRINKLER
 PROTECTED. THESE AREAS APPEAR TO BE
 LOCATED ABOVE THE FIRST FLOOR MECHANICAL
 ROOM.
 F) BACKFLOW DEVICE IS REQUIRED TO BE
 SUPERVISED WITH TAMPER SWITCHES AND
 A CHAIN AND LOCK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910