Plan Review Notes For Permit 02030913 |
Permit Number |
02030913 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-10 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 PRIVATE POOLS | | | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | PRIVATE SWIMMING POOLS. NOTE SAYS FBC | | SECT 104.1 EDT. | | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-4 92. GENERAL NOTE #14 SAYS | | DESIGNED PER WEST PALM BEACH SWIMMING | | POOL CODE. | | 3) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 4) | | FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP- | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | BASE IN A MANNER THAT WILL ELIMINATE | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | AL 4" THICK. (DETAIL) | | 5) | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 6) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 7) | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|