2002-03-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 |
| |
| 1) FBC-2001 SEC 424.2.6.6.2 PLEASE GIVE |
| MANUFACTURE AND MODEL # FOR SELF CLOSING |
| SAFTY COVER ON VACUUM LINE. |
| 2) |
| FBC-2001 SEC 424.2.6.4 SUBMIT MANUFACT- |
| URES RECOMMENDATIONS. |
| 3) |
| FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 4) |
| FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 5) |
| FBC-2001 SEC 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 6) |
| FBC-2001 SEC 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) |
| 7) |
| FBC-2001 SEC 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 8) |
| FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL |
| WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| LED WITH FLANGES OR UNION CONNECTIONS |
| ADJACENT TO THE HEATER. (ADD TO NOTES) |
| 9) |
| FBC-2001 SEC 424.2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| AND PERMIT REQUIRED. (NOTES) |
| |