Plan Review Notes For Permit 02030773 |
Permit Number |
02030773 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-29 00:00:00 | DENIED | | REFERENCE: FBC-2001 | | | | 1) POOL PIPING DIAGRAM, SHOW VENT PIPING | | 2) SEC 4.24.2.7.2 PROVIDE MOUNTING DE- | | TAIL FOR EQUIPMENT. SLAB SHALL BE NOMIN- | | AL 4" | | 3) SEC 4.24.2.9 WATER SUPPLY. ORD 2835- | | 95 - BACKFLOW REQUIRED ON WATER SERVICE. | | (ADD TO NOTES) | | 4) SEC 4.24.2.12 NO AIR TEST FOR PVC. - | | (ADD TO NOTES) | | 5) SEC 4.24.2.13.2 PURPLE CLEANER REQ- | | UIRED FOR PVC. FBC PLMG. SEC 605.21 | | (ADD TO NOTES) | | 6) FOR FUTURE REFERENCE: WHEN POOL HEAT- | | ER IS SUPPLIED, SEC 4.24.2.6.4 MANUF. | | RECOMMENDATION REQUIRED., SEC 4.24.14.2 | | WATER RETENTION - PROVIDE MANUF. CUT | | SHEETS SHOWING COMPLIANCE., SEC 4.24.2. | | 14.4 CONNECTIONS TO HEATER SHALL BE | | FLANGED OR UNIONS. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|