2002-04-15 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02030756 |
| 9031 SAND PINE LANE |
| CONT: NLS COMMUNITIES |
| TEL: (561) 691-1771 |
| |
| FL BLDG CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)- PLANS SUBMITTED AFTER FEB. 28, 2001 |
| SHALL BE DESIGNED TO THE 2001 FLORIDA |
| BUILDING CODE. |
| 2)- DESIGN CRITERIA & FOR BUILDING CODE |
| COMPLIANCE, FL BLDG CODE 1606.1.7 THE IN |
| FORMATION RELATED TO WIND SHALL BE SHOWN |
| ON THE CONSTRUCTION DRAWINGS. |
| 3)- FL BLDG CODE 1909.3 JOINTS (2) |
| EXCEPTION: CONCRETE SLABS ON GRADE |
| CONTAINING 6X6 W1.4XW1.4 WELDED WIRE |
| REINFORCEMENT FABRIC LOCATED IN THE |
| MIDDLE TO THE UPPER 1/3 OF THE SLAB, |
| APPROVED MATERIALS OR SUPPORTS AT SPAC- |
| ING NOT TO EXCEED 3 FT OR IN ACCORDANCE |
| WITH MANUFACTURES SPEC. |
| 4)- SHEET A8 DETAIL #9 SEE FL BLDG CODE |
| 2117.1.1 GABLE ENDWALLS SHALL BE STRUC- |
| TURALLY CONTINUOUS BETWEEN POINTS OF |
| LATERAL SUPPORT. |
| 5)SHEET A-5A SEMCO IS NO LONGER IN BUS- |
| INESS, UPDATE PLANS, USP 2001 CATALOG |
| FOR TAPR 216 VALUE IS 1485 LSB FOR |
| UPLIFT. NOTE WHEN MULTIPLE STRAPS ARE |
| CLOSER THAN 8" A DERATING SHALL OCCUR. |
| SEE MANUFACTURES NOTES, PAGE40. |
| FOR (2) TARP 216 2X 1485=2970X.80%= |
| 2376 LBS NOT 3900 LBS? |
| 6)- TAPR222 THE VALUE OF 1485 FOR ONE |
| STRAP REVISIT THE FIGURES FOR MULTIPLE |
| STRAPS, LETTER SEALED FROM ENGINEER FOR |
| USP GIVING THESE VALUES!!!!! |
| 8)- USP HAS NO RTP 1812? |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X8412 |