2002-08-21 00:00:001) ALL UNDERGROUND FIRE LINES ARE TO
 BE INSTALLED IN ACCORDANCE WITH
 NFPA 24.
  
 2) NO CONTROL VALVES ARE ALLOWED TO BE
 INSTALLED IN THE FIRE DEPARTMENT
 CONNECTION.
  
 3) A CHECK VALVE IS REQUIRED IN THE
 FIRE DEPARTMENT CONNECTION.
  
 4) UNDERGROUND FIRE LINES ARE TO BE
 PROPERLY RESTRAINED IN ACCORDANCE WITH
 NFPA 24.
  
 5) ALL LINES ARE TO BE PRESSURE TESTED
 IN ACCORDANCE WITH NFPA 24.
  