Plan Review Notes For Permit 02030743 |
Permit Number |
02030743 |
|
Review Stop |
FIRE |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2002-08-21 00:00:00 | 1) ALL UNDERGROUND FIRE LINES ARE TO | | BE INSTALLED IN ACCORDANCE WITH | | NFPA 24. | | | | 2) NO CONTROL VALVES ARE ALLOWED TO BE | | INSTALLED IN THE FIRE DEPARTMENT | | CONNECTION. | | | | 3) A CHECK VALVE IS REQUIRED IN THE | | FIRE DEPARTMENT CONNECTION. | | | | 4) UNDERGROUND FIRE LINES ARE TO BE | | PROPERLY RESTRAINED IN ACCORDANCE WITH | | NFPA 24. | | | | 5) ALL LINES ARE TO BE PRESSURE TESTED | | IN ACCORDANCE WITH NFPA 24. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|