Plan Review Notes For Permit 02030743 |
Permit Number |
02030743 |
|
Review Stop |
B |
Sequence Number |
63 |
|
Notes |
Date |
Text |
2003-03-14 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | R.I. JOHNSON & ASSOCIATES SUBMITTAL FOR | | STAIR #3 RAILING CALCS. | | | | FBC 1608.2.2.2THE SUBMITTED | | CALCULATIONS AND TEST REPORT ONLY | | CONSIDER CONCENTRATED LOADING APPLIED | | HORIZONTALLY. IN ADDITION, THE GUARDRAIL | | SHALL BE DESIGNED TO RESIST UNIFORMLY | | DISTRIBUTED LOADS OF 50 LB/FT APPLIED | | HORIZONTALLY TOGETHER WITH A | | SIMULTANEOUS 100 LB/FT APPLIED | | VERTICALLY DOWN AT THE TOP OF THE | | HANDRAIL.SUBMIT FURTHER CALCULATIONS. |
|