2003-03-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 R.I. JOHNSON & ASSOCIATES SUBMITTAL FOR
 STAIR #3 RAILING CALCS.
  
 FBC 1608.2.2.2THE SUBMITTED
 CALCULATIONS AND TEST REPORT ONLY
 CONSIDER CONCENTRATED LOADING APPLIED
 HORIZONTALLY. IN ADDITION, THE GUARDRAIL
 SHALL BE DESIGNED TO RESIST UNIFORMLY
 DISTRIBUTED LOADS OF 50 LB/FT APPLIED
 HORIZONTALLY TOGETHER WITH A
 SIMULTANEOUS 100 LB/FT APPLIED
 VERTICALLY DOWN AT THE TOP OF THE
 HANDRAIL.SUBMIT FURTHER CALCULATIONS.