Plan Review Notes For Permit 02030743 |
Permit Number |
02030743 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2002-07-18 00:00:00 | CORRECTIONS NOT COMPLETE | | | | ADD FIRE DAMPERS TO TWO DUCTS LEAVING | | SHAFT BY OFFICE M-18 ON SHT M-2.04. | | | | NOTE ON M-301 RELIEF TO BE 20 FEET ABOVE | | GRADE ALSO NEEDS TO BE MIN. 15 FEET | | FROM ANY AIR INTAKE OPENING. |
|