2002-07-18 00:00:00CORRECTIONS NOT COMPLETE
  
 ADD FIRE DAMPERS TO TWO DUCTS LEAVING
 SHAFT BY OFFICE M-18 ON SHT M-2.04.
  
 NOTE ON M-301 RELIEF TO BE 20 FEET ABOVE
 GRADE ALSO NEEDS TO BE MIN. 15 FEET
 FROM ANY AIR INTAKE OPENING.