2002-07-16 00:00:00 | BUILDING PLAN REVIEW |
| ******PROVISO******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| --PROVISO-- |
| FBC* 104.2.1.1ROOF COVERING PRODUCT |
| APPROVAL SHALL BE SUBMITTED FOR THE ROOF |
| COVERING SYSTEM TO BE USED (FBC 1504.3) |
| |
| --PROVISO-- |
| FBC 1606.1.4 SUBMIT WINDOW AND DOOR |
| PRODUCT APPROVALS FOR THE EXTERIOR DOOR |
| AND WINDOW SYSTEMS TO BE USED. |
| |
| --PROVISO-- |
| FBC 11-4.9.4(2)STAIRWAY HANDRAILS. |
| SHEET A-810, DETAIL 6.TO AVOID |
| AMBIGUITY, THE DIMENSION LINE MARKERS |
| SHALL POSITION THE ACTUAL INTERSECTION |
| OF HORIZONTAL TO SLOPING HANDRAIL SO |
| THAT THE HANDRAIL CONTINUES TO SLOPE |
| BEYOND THE THE BOTTOM RISER FOR A |
| DISTANCE EQUAL TO THE WIDTH OF ONE TREAD |
| AND THEN EXTENDS HORIZONTALLY FOR 12" |
| (FIG. 19C) |
| |
| --PROVISO-- |
| FBC 11-4.31PUBLIC TELEPHONES. |
| |
| EACH ACCESSIBLE TELEPHONE, AND 25% (BUT |
| NOT LESS THAN ONE) OF THE REMAINING |
| TELEPHONES SHALL BE EQUIPPED WITH VOLUME |
| CONTROL (REF: FBC 11-4.1.3(17)(B)) |
| |
| ONE PUBLIC TEXT TELEPHONE IS REQUIRED |
| (REF: FBC 11-4.1.3(17)(C)(I)) |