2002-06-13 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) PLANS TO BE ROUTED TO DBPR HOTEL AND
 RESTURANT DIVISION FOR PLAN REVIEW BE-
 FORE PLUMBING PLAN REVIEW. (RESPONSE NO-
 TED)
 2) SANITARY PIPE SIZE NOT CORRECT. ONLY
 180 FU FOR 4" PIPE @ 1/8" PER FOOT FALL.
 PLEASE ADJUST PIPE SIZE.(TALKED TO ENG.)
 3) SHT P-401 SANT RISER DIAGRAM FLOOR
 DRAIN AT WATER TO REFLECT FLOOR PLAN &
 SHOW AS FLOOR SINK. (DISCUSSED WITH ENG)
 4) SHT P-402 WATER RISER DIAGRAM, ALL
 WATER HAMMER ARRESTORS NOT LOCATED NEAR
 FIXTURES. PLEASE CHANGE (DISCUSSED WITH
 ENG.)
 5) GAS REVIEW NOT DONE - ENGINEER SAYS
 INFORMATION SHALL BE SUBMITTED WITH GAS
 PERMIT APPLICATION.
 6) CONDENSATE SHALL BE PIPED SEPARATE
 FROM BLDG. SHT P-201 COLS. B/11 EXCEPT-
 ION. (DISCUSSED WITH ENG.)
  