2002-06-07 00:00:00DENIED:
  
 1. M-2.01 NO F/D AT 10X10 DUCT INTO VEST
 SB-004.
 2. M-2.04 NO F/D AT 24X24 DUCT INTO FEC
 SURFACE RM.
 3. M-2.04 NO F/D (X2) AT DUCTS LEAVING
 SHAFTS BY OFFICE M-18.
 4. M1.02 NOTE #9 SHOWS .588 IPLV FLORIDA
 ENERGY CODE MINIMUM IS 5.3 IPLV
  
 PROVISO ITEMS BELOW:
 1. SIGNAGE AT DOORS TO CHILLER ROOM PER
 FBC(M) 1105.1 PROHIBITING ACCESS BY
 OTHERS WILL BE REQUIRED.
 2. EXISTING AHU IN CHILLER ROOM TO BE
 SEALED FBC(M) 1105.4.
 3. TERMINATION OF CHILLER RELIEF PIPING
 SHALL BE PER FBC(M) 1105.9- MINIMUM 15
 FEET ABOVE ADJOINING GRADE AND NOT LESS
 THAN 20 FEET FROM ANY WINDOW,
 VENTILATION OPENING, OR EXIT.