Plan Review Notes For Permit 02030743 |
Permit Number |
02030743 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-06-07 00:00:00 | DENIED: | | | | 1. M-2.01 NO F/D AT 10X10 DUCT INTO VEST | | SB-004. | | 2. M-2.04 NO F/D AT 24X24 DUCT INTO FEC | | SURFACE RM. | | 3. M-2.04 NO F/D (X2) AT DUCTS LEAVING | | SHAFTS BY OFFICE M-18. | | 4. M1.02 NOTE #9 SHOWS .588 IPLV FLORIDA | | ENERGY CODE MINIMUM IS 5.3 IPLV | | | | PROVISO ITEMS BELOW: | | 1. SIGNAGE AT DOORS TO CHILLER ROOM PER | | FBC(M) 1105.1 PROHIBITING ACCESS BY | | OTHERS WILL BE REQUIRED. | | 2. EXISTING AHU IN CHILLER ROOM TO BE | | SEALED FBC(M) 1105.4. | | 3. TERMINATION OF CHILLER RELIEF PIPING | | SHALL BE PER FBC(M) 1105.9- MINIMUM 15 | | FEET ABOVE ADJOINING GRADE AND NOT LESS | | THAN 20 FEET FROM ANY WINDOW, | | VENTILATION OPENING, OR EXIT. |
|