Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2002-06-07 00:00:001) PLAN REVIEW COMMENT RESPONSE 27
 LOCATED ON PAGE 7 OF PERMIT REVIEW
 COMMENTS, 2ND REVIEW SUBMITTAL, APRIL
 22,2002 IS CONFUSING. THE PORTION
 THAT INDICATES "NETS WILL BE ADDED"
 IS NOT VERY CLEAR.
  
 2) EXIT SIGN INFORMATION THAT WAS
 PROVIDED IS ACCEPTABLE. THANK YOU.
  
 3) PLANS STILL INDICATE IMPROPER
 OCCUPANT LOAD FOR ANCILLARY SPACE
 ON PAGE LS-103.
  
 4) THE OCCUPANT LOAD FOR THE MEZZANINE
 IS STILL INCORRECT.
  
 5) DOOR M-17 SHOULD BE SHIFTED IN
 CORRIDOR M-16.
  
 6) PARKING SPACE # 55 AND THE BIKE AREA
 NOTED ON LEVEL 2, PARKING APPEARS TO
 POSE A PROBLEM. PLEASE SCALE THIS AREA
 TO DETERMINE IF THE MINIMUM WIDTH
 REQUIREMENTS ARE MET ESPECIALLY AT THE
 NORTHWEST CORNER OF THE PARKING SPACE.
  
 7) ALL SHAFTS THAT PERSONS CAN FALL INTO
 MUST BE MARKED "SHAFTWAY IN RED LETTERS
 AT LEAST 6 INCHES HIGH ON A WHITE
 BACKGROUND.
  
 8) PLEASE PROVIDE TACTILE SIGNAGE AT
 ALL EXIT DOORS.
  
 9) EXIT SIGNS STILL SHOWN DIRECTING
 AND IMMEDIATELY IN FRONT OF VALET
 RAMP ON LS-102.
  
 10) WITH REGARDS TO THE MAG LOCKS
 PLANNED FOR USE IT WAS INDICATED THAT
 THESE DEVICES WILL BE TIED INTO THE
 FIRE ALARM SYSTEM. PLEASE BE ADVISED
 THAT THERE ARE OTHER CODE REQUIREMENTS
 FOR THESE DEVICES UNDER DELAYED EGRESS
 OR ACCESS CONTROLLED EGRESS.
  
 11) STILL CONFUSED ABOUT "USING THE
 ESCUTHEON ONLY AND CONCEALING THE EYE
 WITH THE COVER NOTES".
  
 12) STRIPING NOTED OUTSIDE OF EXIT DOORS
 ARE NOT NECESSARY UNLESS THE OWNER
 MANDATES THEM, SEE PAGE LS-105.
  
 13) PLEASE SHADE EXIT ACCESS AREAS ON
 THE PLAN FOR EXITS THAT ARE OPPOSITE OF
 PARKING SPACES. THIS APPEARS TO BE A
 PROBLEM ON MORE THAN ONE LOCALE. PLEASE
 SEE LS-101 AND LS-102.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL