Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop B
Sequence Number 3
Notes
Date Text
2002-06-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/28/02:
  
 2) RESPONSE LETTER OF 5/31/02 IS NOTED.
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) RESPONSE LETTER OF 5/31/02 IS NOTED.
 FBC* 104.2.1.1 ROOF COVERING PRODUCT
 APPROVAL SHALL BE SUBMITTED FOR THE ROOF
 COVERING SYSTEM TO BE USED (FBC 1504.3)
  
 7) RESPONSE LETTER OF 5/31/02 IS NOTED.
 FBC 1606.1.4SUBMIT WINDOW AND DOOR
 PRODUCT APPROVALS FOR THE EXTERIOR DOOR
 AND WINDOW SYSTEMS TO BE USED.
  
 9) FBC 13-103THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS SHALL BE AMENDED TO
 SHOW THE PERMITTING OFFICE AS 'WEST PALM
 BEACH' AND THE JURISDICTION NO. AS
 604700.
  
 11) THE ADDITION OF PAINTED STRIPES AND
 EGRESS WARNING ON SHEETS LS-103 AND
 A-103 ARE NOTED.THE ADDITION OF
 PAINTED STRIPES ON SHEET LS-105, SECOND
 LEVEL, WAS NOT REQUIRED AND IS NOT
 NECESSARY.
  
 21) FBC 104.2.1EXTERIOR ALUMINUM
 CLADDING PANELS.THE ADDITION OF
 EXPANSION FASTENERS IS NOTED, BUT THEY
 ARE SHOWN ONLY DIAGRAMMATICALLY.
 ANNOTATE THE DETAIL TO STATE THE TYPE,
 SIZE AND SPACING OF THE FASTENERS.ALSO
 STATE WHETHER THE FASTENING DETAIL IS
 'TYPICAL ', OR IS IT APPLICABLE ONLY TO
 THE 'MEDALLION AND APPLIQUES'?
  
 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING.
 THE NOTE ADDED TO SHEETS LS-101, LS-102,
 A-101 AND A-102 DOES NOT REFER TO
 ACCESSIBILTY, AND SHOULD BE AMENDED TO
 START, "ACCESSIBLE PARKING:IT IS THE
 OWNERS INTENTION......"
  
 24) FBC 11-4.8.3THE LEVEL 1 PARKING
 RAMP UP TO THE ELEVATOR LOBBY SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 36".AMEND THE
 PLAN TO DEMONSTRATE COMPLIANCE.ALSO
 THE LENGTH OF THE RAMP SHALL BE ADDED
 TO ENSURE A MAXIMUM SLOPE OF 1 IN 12.
  
 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS.
 THE RESPONSE LETTER OF 5/31/02 IS NOTED,
 BUT THE DIMENSION LINE MARKERS SHALL
 POSITION THE ACTUAL INTERSECTION OF
 HORIZONTAL TO SLOPING HANDRAIL TO AVOID
 AMBIGUITY.
  
 29) FBC 11-4.31PUBLIC TELEPHONES.
 THE RESPONSE LETTER OF 5/31/02 DOES NOT
 ADDRESS THE TELEPHONES WHICH ARE REMOTE
 FROM THE VICINITY OF THE TOILETS AND
 DRESSING ROOM (EG. PREFUNCTION HALL,
 G-09 TELEPHONE ALCOVE,AND CORRIDOR 2.03)
 ARCHITECT HAS ADVISED THAT REVISED
 SHEETS ARE BEING PREPARED.
  
 30) FBC 11-4.15DRINKING FOUNTAINS.
 THE PLANS SHALL BE AMENDED TO SHOW
 COMPLIANCE WITH THE SPOUT HEIGHT AND
 VERTICAL CLEARANCE REQUIREMENTS
 (FIG. 27A).ARCHITECT HAS ADVISED THAT
 REVISED SHEETS ARE BEING PREPARED.
  
 31) FBC 11-4.19 LAVATORIES. THE REVISION
 TO 11/A-208 IS NOTED.ADD DIMENSIONS TO
 DEMONSTRATE COMPLIANCE WITH THE KNEE
 CLEARANCE DIMENSIONS OF 8" MINIMUMAND
 27" MINIMUM (FIG. 31)
  
 34) FBC 11-4.35 DRESSING ROOMS.THE
 MIRRORS ARE TOO FAR TO AFFORD VIEW TO
 A PERSON ON THE BENCH. ADDITIONAL
 MIRRORS ARE REQUIRED.A SUGGESTED
 LOCATION ON THE 6' HIGH STUD WALLS SHOWN
 ON SECTION 1B/A-209.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499