2002-05-21 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| |
| 1) SHT P-101 ICE MACHINE DETAIL - FILTER |
| SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN |
| FORMATION. |
| 2) SHT P-101 SUBMERSIBLE SUMP PUMP, MAN- |
| UFACTURE INFO SHOWING LISTING REQD. |
| 3) SHTS P-202, 203, ALL |
| CONDENSATE SHALL BE PIPED SEPARATELY TO |
| THE OUTSIDE OF BLDG AND TIED INTO STORM |
| OR DRYWELL. SEE COLS. 14-A/B, 11-B/C |
| SHT P-202. SEE RM #G-05 SHT P-203. |
| 4) SHT P-201, ELEVATOR #1 DRAINS TO RAIN |
| WATER CATCH BASIN AND HAS NO BACKWATER |
| VALVE. ELEVATOR #3 HAS AN AREA DRAIN |
| WITH A BACKWATER VALVE IN LINE AND DIS- |
| CHARGES TO AN OIL AND SAND INTERCEPTOR. |
| PLEASE CHECK WITH ELEVATOR COMPANY TO |
| SEE IF THIS IS ACCEPTABLE TO HOOK UP |
| DIRECTLY IN ELEVATOR PIT. |
| 5) PLEASE ROUTE PLANS THROUGH DEPT OF |
| BUSINESS HOTEL AND RESTURANT DIVISION |
| FOR PLAN REVIEW BEFORE RESUBMITTING FOR |
| PLAN REVIEW. |
| 6) SHT P-302 ITEMS #82/115 FILTERS, NSF |
| APPROVAL REQUIRED. SUBMIT MANUF. INFO |
| 7) PLEASE SHOW FIXTURE UNITS AS THEY |
| ACCUMULATE ON THE SANITARY RISER DIAGRAM |
| 8) SHT P-401 MECH ROOM M-13 FLOOR DRAIN |
| NOT SHOWN ON SANT RISER DIAGRAM. |
| 9) SHT P-401 SANT RISER FOR MECH ROOMS |
| M-13, 2-28, 3-016 NOT SHOWN ON SANT RIS- |
| ER DIAGRAM. PLEASE SHOW RISER AS SHOWN |
| ON FLAT DRAWING IN WOMENS ROOM G-39 & |
| MENS ROOM G-40, PICKING UP ALL MECH RMS |
| AND VENT THROUGH ROOF. |
| 10) SHT P-401 FLOOR DRAIN ON SANT RISER |
| DIAGRAM SHOULD BE CHANGED TO FLOOR SINK |
| AT WATER HEATER. (CHANGED ON FLOOR PLAN) |
| 11) SHT P-402 KITCHEN EQUIP PLMG SCHED., |
| SHOWS 1 FRYER, GAS RISER SHOWS 2. PLEASE |
| CLAIRFY. |
| 12) SHT P-402 WATER RISER DIAGRAM, ALL |
| WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR FIXTURES IN AN "EFFECTIVE RANGE" |
| NOT AT TOP OF DROP. LOCATE PER MANUFACT- |
| URE INSTALLATION INSTRUCTIONS AND PDI- |
| WH 201. (SOME CHANGED NOT ALL) |
| 13) ALL GAS PERMIT APPLICATION REQUIRE- |
| MENTS FROM PREVIOUS REVIEW HAVE NOT BEEN |
| ADDRESSED. PLEASE SUBMIT INFORMATION. |
| 14) SHT A-106 & A-210 CEO TOILET ROOM |
| CAN NOT CHANGE FLOOR PLANS TO COMPLY |
| WITH ADAPTABILITY. STRUCTURAL CHANGES |
| FOR ADAPTABILITY IS NOT APPROVED. |
| PLEASE SHOW DETAILS FOR ADAPTABILITY. |
| SHOWER CURB TO BE NO MORE THAN 1/2", |
| BACKING FOR ALL GRAB BARS, SPACING FOR |
| W/C ECT. |
| 15) TO WHERE DOES THE RAIN WATER FROM |
| THE CANOPY DRAIN? |
| |
| REVIEW BY KEN STEVENS |