Date |
Text |
2002-05-21 00:00:00 | 1) PLEASE EXPLAIN NON-ILLUMINATED EXIT |
| SIGNS NOTED ON PAGE LS-103. PLEASE |
| REVIEW "ILLUMINATIONS OF SIGNS" SECTION |
| 7.10.5.1, LIFE SAFETY CODE 2000 EDITION. |
| |
| 2) THE OCCUPANT LOAD FOR THE ANCILLARY |
| SPACE LOCATED ON PAGE LS-103 IS NOT |
| CORRECT. IT SHOULD READ 52 PERSONS NOT |
| 523 PERSONS. |
| |
| 3) THE OCCUPANT LOAD FOR MEZZANINE LEVEL |
| ON LS-104 IS NOT CORRECT. SHOULD READ |
| 4 OR 5 NOT 45. THE TOTAL OCCUPANT LOAD |
| SHOULD APPROXIMATELY 7 NOT 48. |
| |
| 4) IS THE ELEVATION EQUAL ON BOTH SIDES |
| OF THE EXIT DOORS FROM THE PREFUNCTION |
| AREA ADJACENT TO STAIR # 2. |
| |
| 5) DOORS FROM STORAGE M-02 APPEAR TO |
| SWING TOO FAR INTO CORRIDOR M-03. |
| |
| 6) DOORS ARE NEARLY OPPOSING ONE ANOTHER |
| IN CORRIDOR M-16. |
| |
| 7) ARE GUARDS SHOWN ON RAILING AT |
| REHEARSAL HALL WALKWAY. |
| |
| 8) THE BUILDING ADDRESS IS REQUIRED TO |
| BE INSTALLED ON IT. A MINIMUM OF 6" HIGH |
| NUMBERS ARE REQUIRED. |
| |
| 9) VEHICLE PARKING SPACE # 55 APPEARS TO |
| INTERFERE WITH EXIT ACCESS TO STAIR. |
| |
| 10) DOES THE ROLL-UP SECURITY GRILL |
| SHOWN ON LEVEL 2 INTERFERE WITH ANY |
| EXITING. |
| |
| 11) PLEASE EXPLAIN 6" STEP NEAR FOYER |
| B-004. |
| |
| 12) THE EXITING FOR THE BUILDING STILL |
| APPEARS TO BE CONFUSING. BY TOTALING |
| THE OCCUPANT LOAD EXIT CAPACITIES FOR |
| STAIRS 1,2,AND 4, IT INDICATES 548 |
| PERSONS. ACCORDING TO LS-105 AN EXIT |
| CAPACITY OF 706 PERSONS IS AVAILABLE |
| FOR THE WEST SIDE. WHEN STAIRS 1,AND 4 |
| ARE TOTALED IT INDICATES 382 PERSONS. |
| EAST EXIT CAPACITY ACCORDING TO THE |
| INFORMATION PROVIDED INDICATES 382 |
| PERSONS. WHEN EXAMINING STAIR 2, IT HAS |
| AN EXIT CAPACITY OF 166 PERSONS. IT IS |
| NOT CLEAR IF STAIR 3 IS USED FOR EXITING |
| AS EXIT SIGNS APPEAR TO BE MISSING. THE |
| CONCERN IS THE ABILITY TO EXIT PERSONS |
| FROM THE FLOOR THAT THEY ARE ON, |
| IRRESPECTIVE OF ANY HORIZONTAL EXITS |
| THAT ARE PROVIDED. |
| |
| 13) STAIR 2 HAS AN EXIT CAPACITY OF 166 |
| NOT 66.7 AS NOTED. |
| |
| 14) PLEASE EXPLAIN GALLERIES A AND B. |
| |
| 15) ADDITIONAL EXIT SIGNS MAY BE NEEDED |
| IN CORRIDOR 3-001A. |
| |
| 16) THE STAIRS NEAR THE LOADING DOCK |
| APPEARS TO HAVE A CAPACITY OF 220 |
| PERSONS. A REVIEW WITH ROBERT BROWN, |
| BUILDING PLANS EXAMINER TOOK PLACE. BY |
| USING A CONSERVATIVE FIGURE, THE EXIT |
| CAPACITY GOING THRU DOORS G-22 WAS 401 |
| PERSONS. HOW DOES EXIT DISCHARGE WORK. |
| |
| 17) STAIR 4 EXIT DOOR AT GRADE LEVEL AND |
| DOUBLE DOORS DIRECTLY ADJACENT TO IT |
| OPPOSE ONE ANOTHER. |
| |
| 18) THE FIRE HYDRANT ON A-103 MUST BE |
| PROVIDED WITH 7'- 6" CLEARANCE TO THE |
| FRONT AND SIDES. A MINIMUM OF 4' MUST |
| BE PROVIDED TO THE REAR OF IT. |
| |
| 19) A KNOX-BOX WILL BE REQUIRED. |
| |
| 20) IT WAS NOTED THAT MAG-LOCKS ARE |
| PRESENT ON THE PLANS FOR EXIT DOORS. |
| PLEASE REVIEW DELAYED EGRESS OR ACCESS |
| CONTROLLED EGRESS DOORS OF THE LIFE |
| SAFETY CODE 2000 EDITION. |
| |
| 21) EXIT SIGNS OBSERVED NEAR VALET |
| RAMP. PLEASE SEE PARKING STRUCTURES |
| OF THE LIFE SAFETY CODE, 2000 EDITION. |
| USE OF THE RAMPS FOR EXITING MAY NOT |
| BE APPLICABLE. |
| |
| 22) A NOTE STILL REMAINS ON THE PLANS |
| THAT INDICATES "150LB PICK-UP POINT |
| RECESSED INTO SPRINKLER HEAD ESCUTHEONS |
| WITH COVER". NO ITEMS ARE TO BE |
| CONNECTED TO FIRE SPRINKLER PIPING OR |
| FIRE SPRINKLER HEADS. |
| |
| 23) MIRRORS ARE NOT TO BE PLACED |
| ADJACENT TO EXIT DOORS. |
| |
| 24) STAIR 1 AND STAIR 3 HAVE A TOTAL |
| EXIT CAPCITY OF 292 PERSONS. |
| |
| 25) WHEN LEAVING CONFERENCE ROOM 3-003 |
| AND RECEPTION 3-002 ONLY ONE DIRECTION |
| OF EXIT TRAVEL HAS BEEN IDENTIFIED. |
| PLEASE VERIFY COMMON PATH OF TRAVEL |
| AND DEAD-END REQUIREMENTS. |
| |
| 26) ALL SHAFTWAYS THAT CONNECT TWO OR |
| MORE FLOORS ARE TO BE IDENTIFIED WITH |
| SIGNS STATING "SHAFTWAY" IN RED |
| LETTERS IN RED LETTERS AT LEAST SIX |
| INCHES HIGH ON A WHITE BACKGROUND. |
| |
| 27) WATER CURTAIN SHOWN ON PAGE FP203 |
| DOES NOT PROVIDE PRESCRIPTIVE CODE |
| REQUIREMENT NOTES. |
| |
| 28) PLEASE EXPLAIN NOTES ON PAGE FP203 |
| "EXIST SPRINKLER PIPING AND SPRINKLERS |
| TO BE REMOVED". |
| |
| 29) DOES NOT APPEAR THAT FIRE HOSE |
| VALVE LOCATIONS HAVE BEEN REVISED ON |
| FIRE PROTECTION DRAWINGS. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |