Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop B
Sequence Number 2
Notes
Date Text
2002-05-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/12/02:
  
 1) RESPONSE LETTER OF 4/22/02 IS NOTED.
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) RESPONSE LETTER OF 4/22/02 IS NOTED.
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.4CONTRARY TO THE LETTER
 OF RESPONSE, DATED 4/22/02, NO SIGNED
 AND SEALED SITE SURVEY DRAWING WAS
 SUBMITTED.
  
 4) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC* 104.2.1.1 ROOF COVERING PRODUCT
 APPROVAL SHALL BE SUBMITTED FOR THE ROOF
 COVERING SYSTEM TO BE USED (FBC 1504.3)
  
 7) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC 1606.1.4 WINDOW AND DOOR PRODUCT
 APPROVALS.SUBMIT PRODUCT APPROVALS FOR
 THE EXTERIOR DOOR AND WINDOW SYSTEMS TO
 BE USED.
  
 9) FBC 13-103THREE COPIES OF THE HVAC
 LOAD ANALYSIS WERE RECEIVED BUT ENERGY
 CODE COMPLIANCE FORMS SHALL BE SUBMITTED
 TO DEMONSTRATE COMPLIANCE WITH THE CODE.
  
 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS
 SHEET LS-105, SECOND FLOOR.ADD PAINTED
 STRIPES AND WARNING: FIRE EGRESS, KEEP
 CLEAR, ON SHEETS LS-103 AND A-103,
 BETWEEN DOOR G22 AND THE EXTERNAL RAMP
 AND STEPS.
  
 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED'
 ROOM, SHEET LS-106.IF, AS STATED IN
 THE LETTER OF RESPONSE, THE EGRESS
 CAPACITY HAS BEEN ASSESSED BASED ON
 OFFICE USE, CHANGE THE ROOM DESIGNATION
 FROM 'UNASSIGNED' TO 'OFFICE' ON
 SHEETS LS-106 AND A-106.
  
 17) IT IS NOTED FROM THE LETTER OF
 RESPONSE, DATED 4/22/02, THAT STAIR #3
 IS NOT INTENDED FOR USE AS AN EXIT.
 THEREFOR THE COMMON PATH OF TRAVEL
 (FBC 202 AND FBC 1020.6) FROM COMMUNITY
 CONFERENCE ROOM 3-003 AND RECEPTION
 3-002 MAY EXCEED 100 FT.SHOW THE
 PROPOSED FURNITURE LAYOUT FOR THESE
 ROOMS ON THE LIFE SAFETY PLAN AND SHOW
 THAT THE COMMON PATH OF TRAVEL TO THE
 NORTH SECTION OF CORRIDOR 3-010 DOES NOT
 EXCEED 100 FT.ALTERNATIVELY, AMEND THE
 EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A
 SEPARATE ROUTE VIA CORRIDOR 3-024.
  
 21) FBC 104.2.1 EXTERIOR ALUMINUM
 CLADDING PANELS.THE REVISED DETAIL
 8/A-705 STILL DOES NOT SHOW THE MEANS OF
 ATTACHING THE ALUMINUM FACED PLYWOOD
 PANELS TO THE BUILDING FACADE.
  
 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING.
 ADD A NOTE, TO THE PARKING LEVEL PLANS,
 STATING THAT THE VALET PARKING SERVICE
 WILL BE THE MEANS OF SATISFYING THE
 REQUIREMENT FOR ACCESSIBLE PARKING.
  
 24) FBC 11-4.8LEVEL 1 PARKING, SHEET
 LS-101.CONTRARY TO THE LETTER OF
 RESPONSE, THE ELEVATOR LOBBY IS SHOWN AS
 EL 80'-6", NOT EL 80'-0", SO THERE IS AN
 ELEVATION CHANGE.SHOW/ANNOTATE THE
 RAMP FROM THE PARKING LEVEL UP TO THE
 ELEVATOR LOBBY LEVEL FOR ACCESSIBILITY.
  
 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS.
 SHEET A-810, DETAIL 6 RAIL AT WALL.
 WITH REFERENCE TO THE LETTER OF RESPONSE
 DATED 4/22/02, THE QUOTATION FROM THE
 CODE IS INCOMPLETE.THE PARAGRAPH GOES
 ON TO REQUIRE THAT THE HANDRAIL CONTINUE
 TO SLOPE BEYOND THE BOTTOM RISER FOR A
 DISTANCE EQUAL TO THE WIDTH OF ONE TREAD
 AND THEN EXTEND HORIZONTALLY FOR 12"
 (FIG. 19C).ON SHEET A810, NEITHER THE
 SLOPED OR HORIZONTAL EXTENSIONS ARE
 DIMENSIONED INDIVIDUALLY TO DEMONSTRATE
 COMPLIANCE.
  
 29) FBC 11-4.31PUBLIC TELEPHONES.THE
 RESPONSE RELATING TO 'FOOTPRINT'IS NOTED
 BUT COMPLIANCE SHALL BE DEMONSTRATED BY
 ADDING DIMENSIONS TO THE PLANS,
 INCLUDING SHEET A103 (AT G-03 AND G-09)
 AND SHEET A105 (AT 2-03, TEL. ALCOVE).
 THE PLANS SHALL ALSO BE AMENDED TO SHOW
 THE INSTALLATION HEIGHT AND FACILITIES
 PROVISION GIVEN IN FBC 11-4.1.3(17).
  
 30) FBC 11-4.15DRINKING FOUNTAINS. THE
 RESPONSE RELATING TO 'FOOTPRINT'IS NOTED
 BUT THE PLANS SHALL BE AMENDED TO
 DEMONSTRATE COMPLIANCE WITH THE SPOUT
 HEIGHT AND VERTICAL CLEARANCE
 REQUIREMENTS (FIG. 27A)
  
 31) FBC 11-4.19LAVATORIES.AMEND THE
 PLANS TO SHOW THE LAVATORY LEGROOM
 CLEARANCES AND A MAXIMUM HEIGHT OF 40"
 TO THE BASE OF THE MIRROR (FIG. 31)
  
 32) FBC 11-4.16WATER CLOSET.THE
 REVISIONS TO SHEETS A-208, A-209 AND
 A-210 ARE NOTED, BUT NORTH AND WEST
 ELEVATIONS, 3/A-208, STILL SHOW TOILET
 SEATS AT 20" ABOVE FLOOR.AMEND TO 18".
  
 34) FBC 11-4.35 DRESSING ROOMS, SHEET
 A-209.THE AMENDMENTS MADE ARE NOTED,
 BUT THE PLANS SHALL BE AMENDED TO
 DEMONSTRATE COMPLIANCE WITH 11-4.35.5
 WHICH REQUIRES THE PROVISION OF A
 COMPLIANT FULL LENGTH MIRROR.
  
 35) FBC 403.1.4.1BARS TO COMPLY WITH
 FBC 11-4.5.2.THE PROPOSAL TO PROVIDE
 BAR SERVICE AT ACCESSIBLE SEATING
 ADJACENT EACH BAR IS NOTED.ADD A NOTE
 TO THE PLANS, AT EACH BAR LOCATION, TO
 DEMONSTRATE THE PROVISION OF ACCESSIBLE
 SEATING AND ASSOCIATED BAR SERVICE.
  
 NOTE: COMMENTS 2, 3, 5, 6, 7, 14 AND 17
 FROM THE FIRE DEPARTMENT PLAN REVIEW #2,
 DATED 5/21/02, SHALL ALSO BE ADDRESSED.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499