2002-05-29 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 4/12/02: |
| |
| 1) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| IMPACT FEES MUST BE PAID TO PALM BEACH |
| COUNTY, THE PLANS STAMPED BY THEM AND A |
| COPY OF THE RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) FBC* 104.2.4CONTRARY TO THE LETTER |
| OF RESPONSE, DATED 4/22/02, NO SIGNED |
| AND SEALED SITE SURVEY DRAWING WAS |
| SUBMITTED. |
| |
| 4) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| FBC* 104.2.1.1 ROOF COVERING PRODUCT |
| APPROVAL SHALL BE SUBMITTED FOR THE ROOF |
| COVERING SYSTEM TO BE USED (FBC 1504.3) |
| |
| 7) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| FBC 1606.1.4 WINDOW AND DOOR PRODUCT |
| APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| THE EXTERIOR DOOR AND WINDOW SYSTEMS TO |
| BE USED. |
| |
| 9) FBC 13-103THREE COPIES OF THE HVAC |
| LOAD ANALYSIS WERE RECEIVED BUT ENERGY |
| CODE COMPLIANCE FORMS SHALL BE SUBMITTED |
| TO DEMONSTRATE COMPLIANCE WITH THE CODE. |
| |
| 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS |
| SHEET LS-105, SECOND FLOOR.ADD PAINTED |
| STRIPES AND WARNING: FIRE EGRESS, KEEP |
| CLEAR, ON SHEETS LS-103 AND A-103, |
| BETWEEN DOOR G22 AND THE EXTERNAL RAMP |
| AND STEPS. |
| |
| 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED' |
| ROOM, SHEET LS-106.IF, AS STATED IN |
| THE LETTER OF RESPONSE, THE EGRESS |
| CAPACITY HAS BEEN ASSESSED BASED ON |
| OFFICE USE, CHANGE THE ROOM DESIGNATION |
| FROM 'UNASSIGNED' TO 'OFFICE' ON |
| SHEETS LS-106 AND A-106. |
| |
| 17) IT IS NOTED FROM THE LETTER OF |
| RESPONSE, DATED 4/22/02, THAT STAIR #3 |
| IS NOT INTENDED FOR USE AS AN EXIT. |
| THEREFOR THE COMMON PATH OF TRAVEL |
| (FBC 202 AND FBC 1020.6) FROM COMMUNITY |
| CONFERENCE ROOM 3-003 AND RECEPTION |
| 3-002 MAY EXCEED 100 FT.SHOW THE |
| PROPOSED FURNITURE LAYOUT FOR THESE |
| ROOMS ON THE LIFE SAFETY PLAN AND SHOW |
| THAT THE COMMON PATH OF TRAVEL TO THE |
| NORTH SECTION OF CORRIDOR 3-010 DOES NOT |
| EXCEED 100 FT.ALTERNATIVELY, AMEND THE |
| EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A |
| SEPARATE ROUTE VIA CORRIDOR 3-024. |
| |
| 21) FBC 104.2.1 EXTERIOR ALUMINUM |
| CLADDING PANELS.THE REVISED DETAIL |
| 8/A-705 STILL DOES NOT SHOW THE MEANS OF |
| ATTACHING THE ALUMINUM FACED PLYWOOD |
| PANELS TO THE BUILDING FACADE. |
| |
| 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. |
| ADD A NOTE, TO THE PARKING LEVEL PLANS, |
| STATING THAT THE VALET PARKING SERVICE |
| WILL BE THE MEANS OF SATISFYING THE |
| REQUIREMENT FOR ACCESSIBLE PARKING. |
| |
| 24) FBC 11-4.8LEVEL 1 PARKING, SHEET |
| LS-101.CONTRARY TO THE LETTER OF |
| RESPONSE, THE ELEVATOR LOBBY IS SHOWN AS |
| EL 80'-6", NOT EL 80'-0", SO THERE IS AN |
| ELEVATION CHANGE.SHOW/ANNOTATE THE |
| RAMP FROM THE PARKING LEVEL UP TO THE |
| ELEVATOR LOBBY LEVEL FOR ACCESSIBILITY. |
| |
| 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. |
| SHEET A-810, DETAIL 6 RAIL AT WALL. |
| WITH REFERENCE TO THE LETTER OF RESPONSE |
| DATED 4/22/02, THE QUOTATION FROM THE |
| CODE IS INCOMPLETE.THE PARAGRAPH GOES |
| ON TO REQUIRE THAT THE HANDRAIL CONTINUE |
| TO SLOPE BEYOND THE BOTTOM RISER FOR A |
| DISTANCE EQUAL TO THE WIDTH OF ONE TREAD |
| AND THEN EXTEND HORIZONTALLY FOR 12" |
| (FIG. 19C).ON SHEET A810, NEITHER THE |
| SLOPED OR HORIZONTAL EXTENSIONS ARE |
| DIMENSIONED INDIVIDUALLY TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 29) FBC 11-4.31PUBLIC TELEPHONES.THE |
| RESPONSE RELATING TO 'FOOTPRINT'IS NOTED |
| BUT COMPLIANCE SHALL BE DEMONSTRATED BY |
| ADDING DIMENSIONS TO THE PLANS, |
| INCLUDING SHEET A103 (AT G-03 AND G-09) |
| AND SHEET A105 (AT 2-03, TEL. ALCOVE). |
| THE PLANS SHALL ALSO BE AMENDED TO SHOW |
| THE INSTALLATION HEIGHT AND FACILITIES |
| PROVISION GIVEN IN FBC 11-4.1.3(17). |
| |
| 30) FBC 11-4.15DRINKING FOUNTAINS. THE |
| RESPONSE RELATING TO 'FOOTPRINT'IS NOTED |
| BUT THE PLANS SHALL BE AMENDED TO |
| DEMONSTRATE COMPLIANCE WITH THE SPOUT |
| HEIGHT AND VERTICAL CLEARANCE |
| REQUIREMENTS (FIG. 27A) |
| |
| 31) FBC 11-4.19LAVATORIES.AMEND THE |
| PLANS TO SHOW THE LAVATORY LEGROOM |
| CLEARANCES AND A MAXIMUM HEIGHT OF 40" |
| TO THE BASE OF THE MIRROR (FIG. 31) |
| |
| 32) FBC 11-4.16WATER CLOSET.THE |
| REVISIONS TO SHEETS A-208, A-209 AND |
| A-210 ARE NOTED, BUT NORTH AND WEST |
| ELEVATIONS, 3/A-208, STILL SHOW TOILET |
| SEATS AT 20" ABOVE FLOOR.AMEND TO 18". |
| |
| 34) FBC 11-4.35 DRESSING ROOMS, SHEET |
| A-209.THE AMENDMENTS MADE ARE NOTED, |
| BUT THE PLANS SHALL BE AMENDED TO |
| DEMONSTRATE COMPLIANCE WITH 11-4.35.5 |
| WHICH REQUIRES THE PROVISION OF A |
| COMPLIANT FULL LENGTH MIRROR. |
| |
| 35) FBC 403.1.4.1BARS TO COMPLY WITH |
| FBC 11-4.5.2.THE PROPOSAL TO PROVIDE |
| BAR SERVICE AT ACCESSIBLE SEATING |
| ADJACENT EACH BAR IS NOTED.ADD A NOTE |
| TO THE PLANS, AT EACH BAR LOCATION, TO |
| DEMONSTRATE THE PROVISION OF ACCESSIBLE |
| SEATING AND ASSOCIATED BAR SERVICE. |
| |
| NOTE: COMMENTS 2, 3, 5, 6, 7, 14 AND 17 |
| FROM THE FIRE DEPARTMENT PLAN REVIEW #2, |
| DATED 5/21/02, SHALL ALSO BE ADDRESSED. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |