Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop P
Sequence Number 14
Notes
Date Text
2003-09-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FBC-2001 CHAPTER 1
  
 1) SHT P-201 REVISION SHOWS REVISION #9
 AS LAST REVISION. THE LATEST REVISION,
 SIGNED AND SEALED 8-14-02 HAS REVISIONS
 #'S 10, 11, 12, AND 13. PLEASE CLAIRFY.
 NUMEROUS REVISIONS NOT CLOUDED. ALSO
 TRIANGLE WITH REVISION NUMBER REQUIRED
 AT EACH REVISION. COL. LINE NUMBER AND
 LETTERS REQUIRED FOR REFERENCE.
 2) SHT P-202 SHEET REVISIE HAS INFORMAT-
 ION DELETED THAT WAS APPROVE ON PRIOR
 REVIEWS. WATER LINES, CONDENSATE, RWL'S
 ECT HAVE BEEN DELETED. PLEASE CLAIRFY.
 COL. LINE TO BE SHOWN FOR REFERENCE.
 CLOUD ALL REVISIONS AND INDICATE WITH A
 TRIANGLE NUMBER.
 3) SHT P-202 PIPING FROM PREVIOUS REV-
 IEWS HAS BEEN DELETED. NEW REVISIONS
 HAVE NOT BEEN CLOUDED OR INDICATED.
 4) ALL SHEETS REVISIONS FROM PREVIOUS
 REVISIONS SHALL BE SHOWN AND ALL NEW
 REVISIONS SHALL BE INDICATED WITH CLOUDS
 AND NUMBERED. UNABLE TO FINISH REVISION
 REVIEW.
 5) FEE DUE FOR REVISION - $50 PLUS $60
 FOR SIX SHEETS SUBMITTED FOR REVISION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]