Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT P-101 ICE MACHINE DETAIL-ALL IN-
 DIRECT WASTE SHALL DRAIN TO FLOOR SINK,
 NOT FLOOR DRAIN AS SHOWN
 2) SHT P-101 ICE MACHINE DETAIL - FILTER
 SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN
 FORMATION.
 3) SHT P-101 SUBMERSIBLE SUMP PUMB -
 MANUFACTURE INFORMATION WITH LISTING REQ
 4) SHT P-101 PLMG FIXTURE SCHED AND SPEC
 FUNNEL FLOOR DRAIN NOT APPROVED. DELETE
 5) SHT P-201 SEPARATE PERMIT REQUIRED
 FOR OIL AND SAND INTERCEPTOR - TO BE
 SIZED BY RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE (561) 837-4074.
 6) SHT P-201 SEPARATE PERMIT REQUIRED
 FOR GREASE TRAP - TO BE SIZED BY RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE (561)
 837-4074 WASTE ORD. #2938-96
 7) SHTS P-201, 202, 203, 204, & 205 -
 ALL CONDENSATE FROM A/C SHALL BE PIPED
 SEPARATE TO OUTSIDE OF BLDG AND BE TIED
 INTO SANITARY OR DRYWELL WITH A RELIEF
 VENT INSTALLED AS PIPE EXITS BLDG. (SEE
 COL'S 14-B/C, 14-A/B, 11-B/C - P-202 COL
 2-B/C, 11-B FUNNEL DRAIN NOT APPROVED,
 P-203 COL 11-B CONDENSATE TO JANITOR
 ROVED, 2-A CONDENSATE TO HUB DRAIN NOT
 APPROVED, RM# G-05 COND TO SANT NOT APP-
 ROVED - P-204 COL 1/2 - B/C COND. TO
 SANT NOT APPROVED, COL 2-D CONDENSATE
 FROM WALK IN COOLER SHALL DRAIN TO FLOOR
 SINK, FUNNEL FLOOR DRAIN NOT APPROVED,
 COL 12-C, SHT P-205 COL 1/2 - B/C, SHT
 P-206 IN MECH ROOM, SHT P-207 ELEV ROOM)
 8) SHT P-201, ELEVATOR #1 DRAINS TO RAIN
 WATER CATCH BASIN AND HAS NO BACKWATER
 VALVE. ELEVATOR #3 HAS AN AREA DRAIN
 WITH A BACKWATER VALVE IN LINE AND DIS-
 CHARGES TO AN OIL AND SAND INTERCEPTOR.
 PLEASE CHECK WITH ELEVATOR COMPANY IF
 THIS WILL BE EXCEPTABLE TO HOOK THESE
 UP DIRECTLY TO ELEVATOR PIT.
 9) SHT P-204 WATER HEATER DETAIL, P/T
 RELIEF DISCHARGE SHALL NOT DRAIN TO
 FLOOR DRAIN. FLOOR SINK REQUIRED FOR ALL
 INDIRECT WASTE. FBC 2001 SEC 802.3
 10) SHT P-204 WATER HEATER DETAIL, SHUT
 OFF VALVE REQUIRED ON EACH SIDE OF CIRC.
 PUMP.
 11) SHT P-206 SAFE WASTE DETAIL, NOT
 APPROVED - DELETE
 12) SHT P-301 #'S 24, 25, 26 FUNNEL
 FLOOR DRAIN NOT APPROVED, FLOOR SINK RE-
 QUIRED FOR INDIRECT WASTE. SEC 802.3
 13) ROUTE PLANS THROUGH DEPT OF BUSINESS
 HOTEL AND RESTURANT DIVISION FOR PLAN RE
 VIEW BEFORE RESUBMITTING FOR CONST PLAN
 REVIEW.
 14) PROVIDE CALCULATIONS FOR MINIMUM
 FACILITIES PER FBC-2001 PLUMBING TABLE
 403.1 AND SEC 403.
 15) SHT P-302 ITEMS #82/115 FILTERS, NSF
 APPROVAL REQUIRED. SUBMIT MANUF. INFO.
 16) SHT P-302 ITEM #84 ICE MACHINE W/BIN
 NOT FOUND.
 17) SHT P-302 ITEM #105 PLEASE CALL OUT
 2ND DRAIN BOARD.
 18) SHT P-302 ITEMS #134 & 136 NOT FOUND
 19) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM WITH ALL THE PIPE SIZES AND SHOW
 FIXTURE UNITS AS THEY ACCUMULATE IN SYS-
 TEM.
 20) SHT P-401 ROOM G-20 FLOOR DRAIN NOT
 SHOWN ON SANT RISER DIAGRAM.
 21) SHT P-401 ROOM G-17 MENS FLOOR DRAIN
 NOT SHOWN ON SANT RISER DIAGRAM.
 22) SHT P-401 MECH ROOM FLOOR DRAIN NOT
 SHOWN ON SANT RISER DIAGRAM. NOT FOR CON
 23) SHT P-401 2" WASTE UP BETWEEN ROOM
 2-E11 & #1 ELEVATOR NOT SHOWN ON SANT.
 RISER DIAGRAM.
 24) SHT P-402 KITCHEN EQUIP PLMG SCHED.
 SHOWS 1 FRYER, GAS RISER SHOWS 2. ??
 25) SHT P-402 WATER RISER DIAGRAM, ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT
 AT TOP OF DROP AS SHOWN ON PLANS. LOCATE
 PER MANUFACTURE INSTALLATION INSTRUCTION
 AND PDI-WH 201.
 26) SHT P-403, SHOW PIPE SIZES FOR ALL
 PIPING TO AREA DRAINS. SHOW SQUARE FOOT-
 AGE FOR ALL AREA DRAINS IN SYSTEM. COND.
 TO RUN SEPARATELY OUT OF BLDG AND TIE
 INTO STORM OUTSIDE. SUBMIT CONDENSATE
 RISER, SHOW RELIEF VENT AS COND. EXITS
 BLDG.
 27) SHT P-403 STORM RISER DIAGRAM, PLEA-
 SE PROVIDE SQ FT OF GUTTER DRAINS ADDED
 TO ROOF DRAINS.
 28) SHT P-403 STORM RISER DIAGRAM, UN-
 DERGROUND PIPE AT COLS 14-B/C SHOWS 6",
 THEN 8". PLEASE CLAIRFY
 29) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE IF NATURAL
 GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE.
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 30) SHT A-206 FAMILY TOILETS G-14, G-31,
 AND DETAIL #12. SHOW CLEAR FLOOR SPACE
 FOR HDCP FIXTURES. DOOR SWING SHALL NOT
 OPEN INTO CLEAR FLOOR SPACE OR UNOBSTRUC
 TED TURNING RADIUS. SHOW ON DETAIL.
 31.SHT A-209 DETAIL #8 SHOWS 4 W/C'S
 WEST OF HDCP STALL, DETAIL #3 SHOWS 3
 W/C'SWEST OF HDCP STALL AND 1 EAST IN
 WOMENS TOILET. PLEASE CLAIRFY. ALSO GIVE
 DIMENSIONS FOR 2ND HDCP STALL WITH GRAB
 BARS IN IT.
 32) SHT A-210 DETAIL #11 LAV CAN NOT BE
 ON WALL OPPOSITE OF W/C IN UNISEX TOILET
 66" CLEAR FLOOR SPACE REQUIRED FIG. 28
 33) SHT A-210 DETAILS #1, 5, 8 SHOW
 CLEAR FLOOR SPACE FOR HDCP FIXTURES.
 DOOR CAN NOT OPEN INTO CLEAR FLOOR SPACE
 FOR FIXTURES. ROOMS #3-020, 3-021, AND
 3-009.
 34) SHT A-210 DETAIL #9 SOUTH ELEVATION,
 LAV NOT SHOWN.
 35) SHT A-209 DETAILS #4 & 5 SHOW CONT-
 ROL AREA FOR SHOWER ON DETAILS. 4.21.5
 36) SHT A-209 DETAIL #1 MENS/WOMENS
 DRESSING ROOMS - BENCH REQUIRED SEC
 4.35.4
 37) SHT A-210 DETAILS #6 & 7 SHOW CONT-
 ROL AREA FOR SHOWER ON DETAILS. 4.21.5
 38) SHTS A-106 & A-210 CEO TOILET SHALL
 BE ADAPTABLE PER SEC 4.1.3(11) PROVIDE
 DETAILS
 39) SHT C-8 SEE ATTACHED SHEET FOR APP-
 ROVED GREASE TRAP DETAIL. CITY OF W.P.B
 UTILITY APPROVED.
 40) WHERE DOES RAIN WATER FROM CANOPY
 DRAIN TO?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377