2002-04-09 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| |
| 1) SHT P-101 ICE MACHINE DETAIL-ALL IN- |
| DIRECT WASTE SHALL DRAIN TO FLOOR SINK, |
| NOT FLOOR DRAIN AS SHOWN |
| 2) SHT P-101 ICE MACHINE DETAIL - FILTER |
| SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN |
| FORMATION. |
| 3) SHT P-101 SUBMERSIBLE SUMP PUMB - |
| MANUFACTURE INFORMATION WITH LISTING REQ |
| 4) SHT P-101 PLMG FIXTURE SCHED AND SPEC |
| FUNNEL FLOOR DRAIN NOT APPROVED. DELETE |
| 5) SHT P-201 SEPARATE PERMIT REQUIRED |
| FOR OIL AND SAND INTERCEPTOR - TO BE |
| SIZED BY RODNEY COMPO ENVIRONMENTAL |
| COMPLIANCE (561) 837-4074. |
| 6) SHT P-201 SEPARATE PERMIT REQUIRED |
| FOR GREASE TRAP - TO BE SIZED BY RODNEY |
| COMPO, ENVIRONMENTAL COMPLIANCE (561) |
| 837-4074 WASTE ORD. #2938-96 |
| 7) SHTS P-201, 202, 203, 204, & 205 - |
| ALL CONDENSATE FROM A/C SHALL BE PIPED |
| SEPARATE TO OUTSIDE OF BLDG AND BE TIED |
| INTO SANITARY OR DRYWELL WITH A RELIEF |
| VENT INSTALLED AS PIPE EXITS BLDG. (SEE |
| COL'S 14-B/C, 14-A/B, 11-B/C - P-202 COL |
| 2-B/C, 11-B FUNNEL DRAIN NOT APPROVED, |
| P-203 COL 11-B CONDENSATE TO JANITOR |
| ROVED, 2-A CONDENSATE TO HUB DRAIN NOT |
| APPROVED, RM# G-05 COND TO SANT NOT APP- |
| ROVED - P-204 COL 1/2 - B/C COND. TO |
| SANT NOT APPROVED, COL 2-D CONDENSATE |
| FROM WALK IN COOLER SHALL DRAIN TO FLOOR |
| SINK, FUNNEL FLOOR DRAIN NOT APPROVED, |
| COL 12-C, SHT P-205 COL 1/2 - B/C, SHT |
| P-206 IN MECH ROOM, SHT P-207 ELEV ROOM) |
| 8) SHT P-201, ELEVATOR #1 DRAINS TO RAIN |
| WATER CATCH BASIN AND HAS NO BACKWATER |
| VALVE. ELEVATOR #3 HAS AN AREA DRAIN |
| WITH A BACKWATER VALVE IN LINE AND DIS- |
| CHARGES TO AN OIL AND SAND INTERCEPTOR. |
| PLEASE CHECK WITH ELEVATOR COMPANY IF |
| THIS WILL BE EXCEPTABLE TO HOOK THESE |
| UP DIRECTLY TO ELEVATOR PIT. |
| 9) SHT P-204 WATER HEATER DETAIL, P/T |
| RELIEF DISCHARGE SHALL NOT DRAIN TO |
| FLOOR DRAIN. FLOOR SINK REQUIRED FOR ALL |
| INDIRECT WASTE. FBC 2001 SEC 802.3 |
| 10) SHT P-204 WATER HEATER DETAIL, SHUT |
| OFF VALVE REQUIRED ON EACH SIDE OF CIRC. |
| PUMP. |
| 11) SHT P-206 SAFE WASTE DETAIL, NOT |
| APPROVED - DELETE |
| 12) SHT P-301 #'S 24, 25, 26 FUNNEL |
| FLOOR DRAIN NOT APPROVED, FLOOR SINK RE- |
| QUIRED FOR INDIRECT WASTE. SEC 802.3 |
| 13) ROUTE PLANS THROUGH DEPT OF BUSINESS |
| HOTEL AND RESTURANT DIVISION FOR PLAN RE |
| VIEW BEFORE RESUBMITTING FOR CONST PLAN |
| REVIEW. |
| 14) PROVIDE CALCULATIONS FOR MINIMUM |
| FACILITIES PER FBC-2001 PLUMBING TABLE |
| 403.1 AND SEC 403. |
| 15) SHT P-302 ITEMS #82/115 FILTERS, NSF |
| APPROVAL REQUIRED. SUBMIT MANUF. INFO. |
| 16) SHT P-302 ITEM #84 ICE MACHINE W/BIN |
| NOT FOUND. |
| 17) SHT P-302 ITEM #105 PLEASE CALL OUT |
| 2ND DRAIN BOARD. |
| 18) SHT P-302 ITEMS #134 & 136 NOT FOUND |
| 19) PLEASE SUBMIT A SANITARY RISER DIA- |
| GRAM WITH ALL THE PIPE SIZES AND SHOW |
| FIXTURE UNITS AS THEY ACCUMULATE IN SYS- |
| TEM. |
| 20) SHT P-401 ROOM G-20 FLOOR DRAIN NOT |
| SHOWN ON SANT RISER DIAGRAM. |
| 21) SHT P-401 ROOM G-17 MENS FLOOR DRAIN |
| NOT SHOWN ON SANT RISER DIAGRAM. |
| 22) SHT P-401 MECH ROOM FLOOR DRAIN NOT |
| SHOWN ON SANT RISER DIAGRAM. NOT FOR CON |
| 23) SHT P-401 2" WASTE UP BETWEEN ROOM |
| 2-E11 & #1 ELEVATOR NOT SHOWN ON SANT. |
| RISER DIAGRAM. |
| 24) SHT P-402 KITCHEN EQUIP PLMG SCHED. |
| SHOWS 1 FRYER, GAS RISER SHOWS 2. ?? |
| 25) SHT P-402 WATER RISER DIAGRAM, ALL |
| WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| AT TOP OF DROP AS SHOWN ON PLANS. LOCATE |
| PER MANUFACTURE INSTALLATION INSTRUCTION |
| AND PDI-WH 201. |
| 26) SHT P-403, SHOW PIPE SIZES FOR ALL |
| PIPING TO AREA DRAINS. SHOW SQUARE FOOT- |
| AGE FOR ALL AREA DRAINS IN SYSTEM. COND. |
| TO RUN SEPARATELY OUT OF BLDG AND TIE |
| INTO STORM OUTSIDE. SUBMIT CONDENSATE |
| RISER, SHOW RELIEF VENT AS COND. EXITS |
| BLDG. |
| 27) SHT P-403 STORM RISER DIAGRAM, PLEA- |
| SE PROVIDE SQ FT OF GUTTER DRAINS ADDED |
| TO ROOF DRAINS. |
| 28) SHT P-403 STORM RISER DIAGRAM, UN- |
| DERGROUND PIPE AT COLS 14-B/C SHOWS 6", |
| THEN 8". PLEASE CLAIRFY |
| 29) FOLLOWING INFORMATION REQUIRED FOR |
| GAS PERMIT APPLICATION. |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| GAS CODE. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE. |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE IF NATURAL |
| GAS SPECIFY .5 PSI OR 2 PSI. |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| FUEL GAS CODE. |
| 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| 30) SHT A-206 FAMILY TOILETS G-14, G-31, |
| AND DETAIL #12. SHOW CLEAR FLOOR SPACE |
| FOR HDCP FIXTURES. DOOR SWING SHALL NOT |
| OPEN INTO CLEAR FLOOR SPACE OR UNOBSTRUC |
| TED TURNING RADIUS. SHOW ON DETAIL. |
| 31.SHT A-209 DETAIL #8 SHOWS 4 W/C'S |
| WEST OF HDCP STALL, DETAIL #3 SHOWS 3 |
| W/C'SWEST OF HDCP STALL AND 1 EAST IN |
| WOMENS TOILET. PLEASE CLAIRFY. ALSO GIVE |
| DIMENSIONS FOR 2ND HDCP STALL WITH GRAB |
| BARS IN IT. |
| 32) SHT A-210 DETAIL #11 LAV CAN NOT BE |
| ON WALL OPPOSITE OF W/C IN UNISEX TOILET |
| 66" CLEAR FLOOR SPACE REQUIRED FIG. 28 |
| 33) SHT A-210 DETAILS #1, 5, 8 SHOW |
| CLEAR FLOOR SPACE FOR HDCP FIXTURES. |
| DOOR CAN NOT OPEN INTO CLEAR FLOOR SPACE |
| FOR FIXTURES. ROOMS #3-020, 3-021, AND |
| 3-009. |
| 34) SHT A-210 DETAIL #9 SOUTH ELEVATION, |
| LAV NOT SHOWN. |
| 35) SHT A-209 DETAILS #4 & 5 SHOW CONT- |
| ROL AREA FOR SHOWER ON DETAILS. 4.21.5 |
| 36) SHT A-209 DETAIL #1 MENS/WOMENS |
| DRESSING ROOMS - BENCH REQUIRED SEC |
| 4.35.4 |
| 37) SHT A-210 DETAILS #6 & 7 SHOW CONT- |
| ROL AREA FOR SHOWER ON DETAILS. 4.21.5 |
| 38) SHTS A-106 & A-210 CEO TOILET SHALL |
| BE ADAPTABLE PER SEC 4.1.3(11) PROVIDE |
| DETAILS |
| 39) SHT C-8 SEE ATTACHED SHEET FOR APP- |
| ROVED GREASE TRAP DETAIL. CITY OF W.P.B |
| UTILITY APPROVED. |
| 40) WHERE DOES RAIN WATER FROM CANOPY |
| DRAIN TO? |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |