Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-05 00:00:00**************DENIED********************
  
 1. AHU # 7 HAS NO OUTSIDE AIR VALUE ON
 SCHEDULE.
 2. THE LOCATION AND INSTALLATION DETAILS
 OF ALL FIRE DAMPERS SHALL BE LOCATED ON
 THE PLANS BY THE DESIGNER PER
 2001FBC(M). PLEASE INDICATE ALL FIRE
 DAMPERS IN DUCTS PENETRATING RATED
 WALLS.
 3. M 203 VCV 2 PLAN CFM = 2275. SCHEDULE
 ONLY CALLS FOR 1875 CFM.
 4. M 205 VAV 9 PLAN CFM = 1350. SCHEDULE
 ONLY CALLS FOR 1275 CFM.
 5. M 206 VAV 5 DISTRUIBUTION EXCEEDS
 SCHEDULE
 6. M 206 VAV 15 2 MARKED ON PLAN, NO 14
 INDICATED.
 7. M206 VAV 15 PLAN CFM= 2000. SCHEDULE
 CALLS FOR 1200 CFM.
 8. M 206 (2) VAV 26 SHOWN W/ DIFFERENT
 TOTAL CFM ON PLAN
 9. VAV IN CONFERENCE RM 3-X04 NOT
 MARKED.
 10. DEFINE FUNCTION OF FCU 8 BOTH DROPS
 SHOW SUPPLY AIR, NO PIPING TO UNIT, NO
 CFM.
 11. INDICATE EQUIPMENT ENERGY RATING ON
 SCHEDULE.
 12. BALANCED AIR RETURN PER FBC(M)
 406.1REQUIRED FOR ALL SPACES.
 13. PROVIDE MECHANICAL ROOM DRAWING FOR
 AHU INSTALATION DETAILS AND CLARITY TO
 SHOW SERVICE ACCESS REQUIREMENTS
 INCLUDING COIL PULL AND OTHER REQUIRED
 FLOOR AREA TO BE LEFT OPEN FOR SERVICE.
 14. M 301. PROVIDE INFORMATION ON RELIEF
 PIPING TERMINATION FOR CHILLER
 EQUIPMENT.
 15. PROVIDE REFRIGERANT INFORMATION
 INCLUDING QUANTITIES AND VENTILATION
 CALCULATIONS FOR COMPLIANCE WITH FBC(M)
 CH 11.