2002-03-26 00:00:00 | 1) CONSTRUCTION FENCE SHOWN ON SITE PLAN |
| G-02 MUST NOT INTERFERE WITH ANY |
| EXISTING EXITING FACILITIES OR ANY |
| FIRE PROTECTION EQUIPMENT OR DEVICES. |
| 2) PLEASE PROVIDE EXISTING FIRE HYDRANT |
| LOCATIONS ON SITE PLAN. |
| 3) NEW CONSTRUCTION MUST NOT INTERFERE |
| WITH FIRE RESCUE ACCESS TO THE |
| EXISTING BUILDINGS LOCATED ON THE SITE. |
| 4) PRIOR TO STARTING CONSTRUCTION A |
| SITE INSPECTION IS TO BE PERFORMED BY |
| FIRE RESCUE TO ENSURE THAT TEMPORARY |
| BARRIERS, ETC., DO NOT INTERFERE WITH |
| ANY EXITING. |
| 5) TEMPORARY BARRIER AT EXISTING STAIR |
| # 4 TO BE NON-COMBUSTIBLE. |
| 6) THE REMOVAL OF ANY COVERED WALKS OR |
| PAVERS ARE NOT TO CREATE ANY HAZARDS TO |
| PERSONS UNSING THE EXISTING BUILDINGS. |
| 7) IT APPEARS THAT FIRE DEPT. VALVE |
| BOX IN BLOCKED BY PARKING SPACE # 8 ON |
| LEVEL 1-PARKING. |
| 8) THE SAME CONDITION APPEARS TO EXIST |
| FOR FIRE DEPT. VALVE BY PARKING SPACE |
| # 12 ON LEVEL 2-PARKING. |
| 9) STAIR # 1 AND STAIR # 3 SHOULD BE |
| EQUIPPED WITH FIRE DEPT. VALVES. STAIRS |
| # 1 AND STAIR # 3 PROVIDE COVERAGE FOR |
| OTHER PARTS OF THE BUILDING. |
| 10) PANIC HARDWARE REQUIRED ON ALL EXIT |
| DOORS SUBJECT TO AN OCCUPANCY OF 100 |
| OR MORE PERSONS. |
| 11) ADDITIONAL EXIT SIGNS NEEDED TO |
| DESIGNATE SECOND MEANS OF EGRESS FROM |
| BANQUET ROOMS LOCATED ON THE GROUND |
| LEVEL. |
| 12) PLEASE INDICATE OCCUPANT LOADS FOR |
| ASSEMBLY ROOMS LOCATED ON THE SECOND |
| LEVEL. |
| 13) PLEASE EXPLAIN RATIONALE FOR SINGLE |
| EXIT ARRANGEMENT FOR OFFICE AREA NEAR |
| PROG OFFICE 3-PO3. |
| 14) PLEASE VERIFY THAT EXIT DOOR SWING |
| IS CORRECT IN RECEPTION, WAITING 3-XO1. |
| 15) IDENTIFICATION SIGNS REQUIRED FOR |
| THE STAIR TOWERS. |
| 16) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION INFORMATION FOR WALLS |
| AND CEILINGS. |
| 17) PLEASE EXPLAIN THE FOLLOWING NOTE |
| " 50LB PICK UP POINT 1/4 X 1 DIA EYE |
| BOLTS AT EVERY CROSSING (168 TOTAL) |
| RECESSED INTO SPRINKLER HEAD |
| ESCUTCHEONS WITH COVER" ON PAGE A-307. |
| 18) BUILDING ADDRESS REQUIRED. |
| 19) GUARDS ARE REQUIRED TO PREVENT A |
| SPHERE OF FOUR INCHES TO PASS THROUGH |
| THEM. |
| 20) ARCHITECTURAL PLANS SHOULD INDICATE |
| THE NUMBER OF AIR CHANGES AND THE CFM |
| OF EXHAUST THAT WILL OCCUR IN THE |
| UNDERGROUND PARKING AREA. |
| 21) ARE THE F1E ITEMS IN THE PARKING |
| AREAS EMERGENCY LIGHTING EQUIPMENT. |
| 22) PLEASE SEE NOTE # 4 ON ELECTRICAL |
| PLAN REVIEW. |
| 23) ROOF MANIFOLD(S) ARE REQUIRED. |
| 24) PLEASE EXPLAIN DESIGN FOR WATER |
| CURTAIN SHOWN ON PAGE FP-203. |
| 25) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR HOOD, DUCT AND EXTINGUISHING SYSTEMS |
| 26) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FOR FIRE ALARM SYSTEM INSTALLATION. |
| 27) ELEVATORS TO COMPLY WITH FLORIDA |
| ELEVATOR CODE 61C-5. |
| 28) PLEASE INDICATE ON PLANS SMOKE |
| DETECTORS FOR ELEVATOR RECALL. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |