Plan Review Notes
Plan Review Notes For Permit 02030743
Permit Number 02030743
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-03-26 00:00:001) CONSTRUCTION FENCE SHOWN ON SITE PLAN
 G-02 MUST NOT INTERFERE WITH ANY
 EXISTING EXITING FACILITIES OR ANY
 FIRE PROTECTION EQUIPMENT OR DEVICES.
 2) PLEASE PROVIDE EXISTING FIRE HYDRANT
 LOCATIONS ON SITE PLAN.
 3) NEW CONSTRUCTION MUST NOT INTERFERE
 WITH FIRE RESCUE ACCESS TO THE
 EXISTING BUILDINGS LOCATED ON THE SITE.
 4) PRIOR TO STARTING CONSTRUCTION A
 SITE INSPECTION IS TO BE PERFORMED BY
 FIRE RESCUE TO ENSURE THAT TEMPORARY
 BARRIERS, ETC., DO NOT INTERFERE WITH
 ANY EXITING.
 5) TEMPORARY BARRIER AT EXISTING STAIR
 # 4 TO BE NON-COMBUSTIBLE.
 6) THE REMOVAL OF ANY COVERED WALKS OR
 PAVERS ARE NOT TO CREATE ANY HAZARDS TO
 PERSONS UNSING THE EXISTING BUILDINGS.
 7) IT APPEARS THAT FIRE DEPT. VALVE
 BOX IN BLOCKED BY PARKING SPACE # 8 ON
 LEVEL 1-PARKING.
 8) THE SAME CONDITION APPEARS TO EXIST
 FOR FIRE DEPT. VALVE BY PARKING SPACE
 # 12 ON LEVEL 2-PARKING.
 9) STAIR # 1 AND STAIR # 3 SHOULD BE
 EQUIPPED WITH FIRE DEPT. VALVES. STAIRS
 # 1 AND STAIR # 3 PROVIDE COVERAGE FOR
 OTHER PARTS OF THE BUILDING.
 10) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
 11) ADDITIONAL EXIT SIGNS NEEDED TO
 DESIGNATE SECOND MEANS OF EGRESS FROM
 BANQUET ROOMS LOCATED ON THE GROUND
 LEVEL.
 12) PLEASE INDICATE OCCUPANT LOADS FOR
 ASSEMBLY ROOMS LOCATED ON THE SECOND
 LEVEL.
 13) PLEASE EXPLAIN RATIONALE FOR SINGLE
 EXIT ARRANGEMENT FOR OFFICE AREA NEAR
 PROG OFFICE 3-PO3.
 14) PLEASE VERIFY THAT EXIT DOOR SWING
 IS CORRECT IN RECEPTION, WAITING 3-XO1.
 15) IDENTIFICATION SIGNS REQUIRED FOR
 THE STAIR TOWERS.
 16) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 17) PLEASE EXPLAIN THE FOLLOWING NOTE
 " 50LB PICK UP POINT 1/4 X 1 DIA EYE
 BOLTS AT EVERY CROSSING (168 TOTAL)
 RECESSED INTO SPRINKLER HEAD
 ESCUTCHEONS WITH COVER" ON PAGE A-307.
 18) BUILDING ADDRESS REQUIRED.
 19) GUARDS ARE REQUIRED TO PREVENT A
 SPHERE OF FOUR INCHES TO PASS THROUGH
 THEM.
 20) ARCHITECTURAL PLANS SHOULD INDICATE
 THE NUMBER OF AIR CHANGES AND THE CFM
 OF EXHAUST THAT WILL OCCUR IN THE
 UNDERGROUND PARKING AREA.
 21) ARE THE F1E ITEMS IN THE PARKING
 AREAS EMERGENCY LIGHTING EQUIPMENT.
 22) PLEASE SEE NOTE # 4 ON ELECTRICAL
 PLAN REVIEW.
 23) ROOF MANIFOLD(S) ARE REQUIRED.
 24) PLEASE EXPLAIN DESIGN FOR WATER
 CURTAIN SHOWN ON PAGE FP-203.
 25) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT AND EXTINGUISHING SYSTEMS
 26) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FOR FIRE ALARM SYSTEM INSTALLATION.
 27) ELEVATORS TO COMPLY WITH FLORIDA
 ELEVATOR CODE 61C-5.
 28) PLEASE INDICATE ON PLANS SMOKE
 DETECTORS FOR ELEVATOR RECALL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910