2002-03-14 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER
 CALCULATIONS SHOWING PRE-CONSTRUCTIONS
 VS POST-CONSTRUCTION DISCHARGE RATE FOR
 THE SITE.
 2. PLEASE PROVIDE HYDRAULIC CALCULATIONS
 SHOWING THE REQUIRED RCP SIZES.
 3. PLEASE SHOW ALL THE EXISTING FIRE HYD
 ON SITE/NEARBY, ADDITIONAL FIRE HYD MAY
 BE REQUIRED.
 4. PLEASE VERIFY, IF CONSTRUCTIONS OF
 18" RCPS FROM S-8 TO S-9 AND TO S-10 AS
 SHOWN WOULD BE IN CONFLICT WITH
 CONSTRUCTION OF AUGER CAST PILES AND THE
 PROPOSED BUILDING'S FOUNDATION.
 5. PLEASE SHOW CONNECTION FOR DOMESTIC
 WATER.
 6. PLEASE SHOW CONNECTION FOR THE
 PROPOSED OIL/WATER SEPARATOR.
 7. CONTRACTOR MUST CALL RODNEY COMPO,
 837-4051 EXT. 4074 FOR APPROVAL,
 INSPECTIONS OF BOTH GREASE/WATER, OIL/
 WATER SEPARATOR.
 8. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM THE CITY
 ENGINEER'S OFFICE, 659-8040.
 9. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDERGROUND /SITE WORKS WILL BE
 REQUIRED AT THE TIME OF ACTUAL
 PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096