2002-03-14 00:00:00 | FAILED : |
| 1. PLEASE PROVIDE STORM WATER |
| CALCULATIONS SHOWING PRE-CONSTRUCTIONS |
| VS POST-CONSTRUCTION DISCHARGE RATE FOR |
| THE SITE. |
| 2. PLEASE PROVIDE HYDRAULIC CALCULATIONS |
| SHOWING THE REQUIRED RCP SIZES. |
| 3. PLEASE SHOW ALL THE EXISTING FIRE HYD |
| ON SITE/NEARBY, ADDITIONAL FIRE HYD MAY |
| BE REQUIRED. |
| 4. PLEASE VERIFY, IF CONSTRUCTIONS OF |
| 18" RCPS FROM S-8 TO S-9 AND TO S-10 AS |
| SHOWN WOULD BE IN CONFLICT WITH |
| CONSTRUCTION OF AUGER CAST PILES AND THE |
| PROPOSED BUILDING'S FOUNDATION. |
| 5. PLEASE SHOW CONNECTION FOR DOMESTIC |
| WATER. |
| 6. PLEASE SHOW CONNECTION FOR THE |
| PROPOSED OIL/WATER SEPARATOR. |
| 7. CONTRACTOR MUST CALL RODNEY COMPO, |
| 837-4051 EXT. 4074 FOR APPROVAL, |
| INSPECTIONS OF BOTH GREASE/WATER, OIL/ |
| WATER SEPARATOR. |
| 8. ANY WORK WITHIN PUBLIC R.O.W WILL |
| REQUIRE A SEPARATE PERMIT FROM THE CITY |
| ENGINEER'S OFFICE, 659-8040. |
| 9. A SEPARATE PERMIT APPLICATION AND |
| FEES FOR UNDERGROUND /SITE WORKS WILL BE |
| REQUIRED AT THE TIME OF ACTUAL |
| PERMITTING. |
| IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| EXT. 8492 MOHAMMAD R. AMINI |